CONSTRUCTION NOTES
UNLESS OTHERWISE SPECIFIED ON THE WORKING DRAWING WHICH FORMS A PART OF THE SPECIFICATION, THE CONTRACTOR /DEVELOPER
SHALL FURNISH THE FOLLOWING ITEMS AT NO COST TO THE CITY OF RANCHO CUCAMONGA.
THE ENGINEER HAS ATTEMPTED TO CORRECTLY SHOW ALL EXISTING UTILITIES AND SUBSTRUCTURES
IN THE VICINITY OF THE WORK, BUT DOES NOT GUARANTEE THERE ARE NO OTHER SUBSTRUCTURES IN THE AREA.
FAILURE OF THE ENGINEER TO SHOW ALL SUBSTRUCTURES IN THEIR CORRECT LOCATION WILL NOT BE A BASIS FOR A CLAIM FOR EXTRA WORK,
AND THE CONTRACTOR SHALL BE RESPOSNBLE FOR ALL DAMAGES TO SUBSTRUCTURES WHETHER SHOWN OR NOT.
1. CONDUIT-
A. MINIMUM COVER IN STREET OR PARKWAY IS 30` BELOW GUTTER GRADE, UNLESS NOTED OTHERWISE.
B. MINIMUM COVER ON PRIVATE PROPERTY IS 30" BELOW FINISHED GRADE, UNLESS NOTED OTHERWISE.
C. CONTRACTOR IS TO FURNISH AND INSTALL APPROVED CONDUIT TO CITY SPECIFICATIONS PER UGS- 100.1, 110 AND 120.
D. FOR THE TYPE OF CONDUIT FOR THIS JOB, SEE CITY SPECIFICATIONS.
E. CAP ALL MAINLINE CONDUITS AND SERVICE CONDUITS PER CITY SPECIFICATIONS.
F. INSTALL BLANK CONDUIT PLUGS IN ALL CONDUITS TERMINATING INTO VAULTS} MANHOLES. PMH'S, SOE'S & ALL CAP LOCATIONS,
PER CITY SPECIFICATIONS.
G. INSTALL PULL ROPE IN ALL CONDUIT RUNS. PULL ROPE TO BE 3/16' POLYPROPYLENE OR POLYETHYLENE ROPE, BRAIDED
OR TWISTED.
H. ALL CONDUIT MUST BE MANDRELLED WITH A CITY APPROVED MANDRELL.
2. CONDUIT RADIUS REQUIREMENTS:
A. THE MINIMUM RADIUS FOR BENDS ARE:
36" FOR CONDUITS 3" IN DIAMETER OR SMALLER
48" FOR CONDUITS 4" AND 5" IN DIAMETER
60" FOR 6" DIAMETER CONDUIT
B: THE MINIMUM RADIUS FOR ALL SWEEPS OF ALL MAINLINE CONDUITS IS 12' -6" (UNLESS NOTED OTHERWISE).
3. EXCAVATION AND BACKFILL:
A. WORK AREA SHALL BE CLEARED AND ROUGH GRADED TO WITHIN FOUR INCHES OF FINAL GRADE PRIOR TO INSTALLATION OF
CITY CONDUIT OR STRUCTURES.
B. ALL EXCAVATIONS SHALL BE IN ACCORDANCE WITH THE CALIFORNIA STATE CONSTRUCTION SAFETY ORDERS (WHEN APPLICABLE),
CITY SPECIFICATIONS, AND ALL GOVERNING LOCAL ORDINANCES.
C. EACH TRENCH TO BE A UNIFORM DEPTH BELOW FINAL GRADE PRIOR TO INSTALLATION OF CITY CONDUIT OR STRUCTURES.
D. SACKFILL SHALL BE PROVIDED BY THE CONTRACTOR FOR ALL EXCAVATIONS AND SHALL INCLUDE CRUSHED ROCK, CONCRETE,
AND /OR IMPORTED BACKRLL, WHEN REQUIRED.
E. BACKFILL WITH A MINIMUM OF ONE SACK PER YARD SAND CEMENT SLURRY AROUND AND OVER VAULTS AND MANHOLES
AND AROUND PMH'S WITHIN ONE FOOT OF FINISHED GRADE.
F. BACKFILL, PER AGENCY SPECIFICATIONS, SHALL IMMEDIATELY FOLLOW SUBSTRUCTURE INSTALLATION. AT NO TIME
SHALL CABLE BE LEFT EXPOSED OVER 24 HOURS.
G. N0 ROCKS ARE ALLOWED WITHIN 12 INCHES OF DIRECT— BURIED CABLES OR ANY CONDUIT WITHOUT CONCRETE ENCASEMENT.
NATIVE BACKFILL CAPABLE OF PASSING THROUGH A ONE —HALF INCH MESH SCREEN SHALL BE CONSIDERED TO BE "ROCK FREE ".
IF EXISTING BACKFILL DOES NOT PASS THROUGH A 1/2" SCREEN. PLACE IMPORTED SAND 3" BELOW AND 12" ABOVE CITE
CABLES. AFTER THIS POINT, NO ROCKS LARGER THAN 12" DIAMETER ARE PERMITTED.
H. ALL BACKFILL SHALL BE COMPACTED TO MEET OR EXCEED LOCAL: ORDINANCES OR OTHER REQUIREMENTS. IT SHALL BE PLACED
IN A MANNER THAT WILL NOT DAMAGE THE CONDUIT OR SUBSTRUCTURE OR ALLOW FUTURE SUBSIDENCE OF THE TRENCH OR
STRUCTURES..
4. PAVING:
REPAVING, WHERE REQUIRED. SHALL BE PLACED IN SUCH A MANNER THAT INTERFERENCE WITH TRAFFIC, INCLUDING
PEDESTRIAN TRAFFIC, WILL BE KEPT TO A MINIMUM. THE CONTRACTOR SHALL ESTABLISH A PROGRAM OF REPAVING ACCEPTABLE
TO THE MUNICIPALITY, COUNTY, OR OTHER AUTHORITY HAVING JURISDICTION AND WHICH IS ACCEPTABLE TO CITY.
5. STRUCTURES:
A. ALL SUBSTRUCTURES SHALL BE CONSTRUCTED OR INSTALLED TO CITY SPECIFICATIONS,
B. INSTALL PROTECTION BARRIERS WHEN REQUIRED IN AREAS EXPOSED TO TRAFFIC, PER CITY INSPECTOR.
C. ALL CONDUIT LINES AND CONCRETE FLOORED SUBSTRUCTURES SHALL BE WATER TIGHT.
D. ALL GROUNDING MATERIALS SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.
E. CONTRACTOR TO PROVIDE SUBSTRUCTURE ENCLOSURE WALL DETAILS TO CITY INSPECTOR FOR APPROVAL PRIOR TO INSTALLATION.
6. RETAINING WALLS:
WHEN REQUIRED, RETAINING WALLS SHALL BE PROVIDED BY THE CONTRACTOR. WALLS ARE REQUIRED WHEREVER GRADE RISES
MORE THAN 18 INCHES ABOVE THE STRUCTURE OR 24" ABOVE THE PAD SURFACE AT A DISTANCE OF 5 FEET FROM THE SAME,
OR IN AREAS SUBJECT TO EROSION. DESIGN AND INSTALLATION MUST COMPLY WITH LOCAL BUILDING ORDINANCES-
REFER TO CITY INSPECTOR FOR TYPICAL SPACE REQUIREMENTS.
7. PERMITS:
ALL PERMITS NECESSARY FOR EXCAVATION SHALL BE PROVIDED BY THE CONTRACTOR.
8. ACCESS:
HEAVY TRUCK ACCESS SHALL BE MAINTAINED TO EQUIPMENT LOCATIONS. STRUCTURES MUST BE CLEAR OF ALL APPURTENANCES
THAT WOULD OBSTRUCT THE LOADING OR UNLOADING OF EQUIPMENT.
9. SERVICES:
A. METERS AND SERVICES SHALL COMPLY WITH CITY SERVICES REQUIREMENTS.
B. WIRING MUST BE IN ACCORDANCE WITH APPLICABLE LOCAL. ORDINANCES AND APPROVED BY LOCAL INSPECTION AUTHORITIES.
10. LOCATION:
A. THE LOCATION OF EXCAVATIONS AND STRUCTURES FOR CITY SHALE. BE AS SHOWN ON THE WORKING DRAWING. NO DEVIATION
FROM THE PLANNED LOCATIONS WILL BE PERMITTED UNLESS APPROVED BY THE CITY INSPECTOR.
S. ACTUAL LOCATION OF OBSTRUCTIONS, STORM DRAINS, AND /OR OTHER FOREIGN UTILITIES TO BE THE RESPONSIBILITY OF THE
CONTRACTOR.
11. CONTRACTOR IS TO VERIFY LOCATION AND WIDTHS OF ALL SIDEWALKS AND DRIVEWAYS PRIOR TO STREET LIGHT INSTALLATION.
WITH THE APPROVED STREET IMPROVEMENT PLANS, APPROVED STREET LIGHT PLANS AND THE ACTUAL FIELD CONDITIONS.
12. SURVEY:
SURVEYING OF STREET IMPROVEMENTS SHALL BE PERFORMED BY CONTRACTOR, PROPERTY CORNERS, LOT LINES, FINISHED GRADE, ETC.,
NECESSARY FOR THE INSTALLATION OF UNDERGROUND FACILITIES MUST BE COMPLETED AND MARKERS OR STAKES PLACED PRIOR TO THE
START OF THE INSTALLATION. IN ADDITION, CONTRACTOR SHALL MAINTAIN THE MARKERS DURING THE INSTALLATION AND INSPECTION BY
INSPECTION BY AGENCY. GRADE AND PROPERTY LINE STAKES MUST SHOW ANY OFFSET MEASUREMENTS..
13, COORDINATION AND SUPERVISION:
THE CONTRACTOR SHALL PROVIDE SUPERVISION OVER AND COORDINATION AMONG THE VARIOUS CONTRACTORS WORKING WITHIN THE
DEVELOPMENT IN ORDER TO PREVENT DAMAGE TO CITY FACILITIES. HE IS RESPONSIBLE FOR THE COST OF REPAIRS, RE-
PLACEMENT, RELOCATION, OR OTHER CORRECTIONS TO CITY FACILITIES MADE NECESSARY BY HIS FAILURE TO PROVIDE
SUPERVISION OR TO OTHERWISE COMPLY WITH THESE SPECIFICATIONS.
14. TELEPHONE AND OTHER UTILITY REQUIREMENTS:
THE DRAWING PREPARED FOR THIS JOB MAY ALSO COVER THE FACILITIES TO BE INSTALLED FOR THE TELEPHONE COMPANY
AND /OR OTHER UTILITY. ANY QUESTIONS CONCERNING DETAILS OF THEIR INSTALLATION SHOULD BE REFERRED TO THE COMPANY
CONCERNED.
16. WARRANTY:
CONTRACTOR EXPRESSLY REPRESENT AND WARRANT THAT ALL WORK PERFORMED AND ALL MATERIAL USED IN MEETING CONTRACTOR'S
OBLIGATIONS HEREIN ARE FREE FROM DEFECTS IN WORKMANSHIP AND ARE IN CONFORMITY WITH AGENCY
REQUIREMENTS. THIS WARRANTY SHALL COMMENCE UPON RECEIPT BY CONTRACTOR OF CITY'S FINAL ACCEPTANCE
AND SHALL EXPIRE ONE YEAR FROM THAT DATE. CONTRACTOR AGREES TO PROMPTLY CORRECT TO THE CITY'S SATISFACTION
AND THAT OF ANY GOVERNMENTAL AGENCY HAVING JURISDICTION AND AT CONTRACTOR'S EXPENSE ANY BREACH OF THIS WARRANTY
WHICH MAY BECOME APPARENT THROUGH INSPECTION OR OPERATION OF UNDERGROUND ELECTRIC SYSTEM BY CITY DURING THIS
WARRANTY PERIOD.
17. INSPECTION:
INSPECTION IS REQUIRED DURING THE CONSTRUCTION PERIOD. A 48 HOUR ADVANCE NOTICE OF INTENT TO START CONSTRUCTION
IS REQUIRED FROM THE CONTRACTOR TO THE CITY OF RANCHO CUCAMONGA PHONE:909 -477 -2740 X4018
18. AS— BUILTS:
CONTRACTOR RESPONSIBLE TO MAINTAIN AS —BUILT DRAWINGS WHICH ARE TO BE UPDATED DAILY.
CONTRACTORS SHALL KEEP AND MAINTAIN TWO COPIES OF THE AS— BUILTS. ONE SET IS FOR THE CONTRACTOR
AND THE SECOND SET IS FOR THE CITY INSPECTOR.
GENERAL NOTES
1. UNLESS OTHERWISE NOTED, ALL WORK SHALL BE DONE IN ACCORDANCE
WITH THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION„
CURRENT EDITION WITH All. CURRENT SUPPLEMENTS, PUBLISHED DY
BUILDING NEWS INC., LOCATED AT 1612 S. CLEMENTINE STREET, ANAHEIM CA
AND APPROPRIATE STANDARD DRAWINGS.
2- PRIOR TO BEGINNING ANY WORK, THE CONTRACTOR SHAH OBTAIN A PERMIT
FROM THE CITY OF RANCHO CUCAMONGA, OFFICE AT
909 - 477 -2740 x4O18
3. ALL WORK COVERED BY THIS PLAN SHALL BE INSPECTED BY THE CITY
ENGINEER. REQUEST FOR INSPECTION SERVICE SHALL BE MADE 24 —HWRS
IN ADVANCE AT 909 -477 -2740 x4018
4.48—HOURS PRIOR TO ANY WORK, THE CONTRACTOR SHALL CALL
THE UNDERGROUND SERVICE ALERT AT 1 (800) 422 -4133 AND OBTAIN
AN INQUIRY IDENTIFICATION NUMBER.
5. ALL MANHOLES SHAM BE ADJUSTED TO FINISHED GRADE IN ACCORDANCE
WITH SECTION 301 -1.6 OF THE STANDARD SPECIFICATIONS FOR PUBLIC
WORKS CONSTRUCTION.
6. THE CONTRACTOR SHALL PROTECT AND RESTORE EXISTING UTILITIES AND
IMPROVEMENTS AS PER SECTION 5 -1, 5 -2, AND 7 -9 OF THE STANDARD
SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION.
7. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL
UTILITIES OF EVERY NATURE, WHETHER SHOWN HEREON OR NOT, TO PROTECT
THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR THE TOTAL EXPENSE
NE �DED� BY OPERAntNS
CONNECTION WITH PROSECUTION OFT WORK
UTILITY OWNERS:
CITY OF RANCHO CUCAMONGA
10500 CIVIC CENTER DR
RANCHO CUCAMONGA, CA 91729
909 -477 -2740 x4018
RANCHO CUCAMONGA
LJ_HILLSI UE R i
1 W LSO AVE
C.
CL
r
1�Q Av r Y
-X 19TH Email l " V Q
0�
3
[ N RBC L!h!
T L-
SHEET NO.
DESCRIPTION
------
1
TITLE SHEET
•! �_ _ -- � _
®_
CIR
CIR 4(KB4)
ARBORS SUBSTATION (66 12KV)
TYPICAL TRENCH DETAILS
A
CIR MA2)
CIR 30CA0
8273 ROCHESTER AVENUE
L 3 -s>400
GTR 50(NEW)
I
RCE woe a
7'xl4'xW
RCMU ELECTRIC CABLE PLAN
I
sb-- = ELBOW
ELBOW RCE GM
� ,I,IVII -- —
Lr�vlt
-- 2
3-- am ELBOW
�__
__ 3
.,Nw tl
1
1
4
II
� -
l DC
2
l
VC 3�- SM c
T
we
.— _ _ _ _ _ _
— JACK BIENNY DRIU _
RCE Ogg
r Va r
RCE OM
T x4
IMMAN
om
I 1 -FJ
I
1 j..
1 1�
I I
I I
RCE 0123
Y sTa' swl..c
6- 600A ELBOW
RCE 0317
5'XIW6'X7'
6--600A ELBOW
3 41000 710'
RCE 0318
5'X10'6'X7'
6 -600A ELBOW
VICINITY MAP
NOT TO SCALE
tih
3 -5' STUB
FOR FUTURE
ROUTE
3 - #1000 1013'
_ - -y 3 -#1000 123'J` 1.. ---
11 -L 0
L.BOW $ 3 -5' STUB 6
FOR FUTURE:
FOR FUTURE
SHEET INDEX
SECTION
SHEET NO.
DESCRIPTION
1
TITLE SHEET
TYPICAL STREET SECTIONS
2
TYPICAL TRENCH DETAILS
ARROW ROUTE
3-5
RCMU ELECTRIC CABLE PLAN
I
RCE 0323 RCE 0324
5'X10'6'X7' 5'XIO'6'X7' I
6 -600A ELBOW 6 -600A ELBOW
3- #10001235' - 3- 41000IU6'
RCE 0327
- L 5'Xi0'6`X7'
2 -5' STUB 1
FOR FUTURE �, SURE
2 3 -#1000 256' 3- #1000 3'
24
3- #1000 256' 3-#1000 a n w ro
RCE 0321 ` 5 `
1- PIE -I1CL 1-
6 -600A ELBOW 6 -600A A E ELBOW
LEGEND OF CONDUIT SYMBOLS
ELECTRIC
ND, CONDUIT REVD. SIZE OF CONDUIT
-�--- LENGTH OF TRENCH
FULL ENCASEMENT IS REQUIRED FOR
ALL ELECTRIC CONDUIT
SAMPLE OF VENDORS:
CONCRETE PRODUCTS
Precast concrete Item complete with necking,cover,and
inserts may be obtained from any of the following
approved manufacturers.
JENSEN PRECAST
14221 San Bernardino Ave., Fontana, Calif. 92335
Phone: (909) 350 -4111
UTILITY VAULT CO.
10650 Hemlock Ave., Fontana, Calif. 92335
Phone: (909) 350 -2675
(909) 428 -3700
BID SET 3/10/14
X
<FOR 2 OR
TRENCH AND REPAIR PAVEMENT
PER CITY STANDARD 120
"DUCT SPACING SYSTEM --
CARLON SNAP -LOC OR
APPROVED EQUAL
.A.B. (PER CITY STANDARDS)
.2 SACK CEMENT ENCASEMENT
TYPICAL. RCMU ELECTRIC ONLY TRENCH
NO SCALE
NORTH SOUTH
R/W R/W
T YPICAL STREET SECTION
ARROW ROUTE
N. T. S.
NORTH
R/W
SOUTH
R/W
TYPICAL STREET SECTION
ARROW ROUTE
(WITHIN THE CALTRANS ROW)
N. T. S.
POLYMER CONCRETE PAD
FOR SURFACE - -MOUNTED TRANSFORMERS,
48''x 54'
PAD P -4 APPROXIMATE
3' MIN WORKING WEIGHT -125 LB 3' MIN WORKING
CLEARANCE FROM CLEARANCE FROM
EDGE OF PAD HOLD -DOWN BRACKET
(NON -DOR SIDE) (SEE NOTE 2.) EDGE OF PAD
(NON -DOR SIDE)
6'-- 54'
CABLE
PLACEMENT 18,
(SEE FIG. 1
AND FIG. 2) 6'
7'
11' 26' lY
48'
Do-
8' MIN WORKING CLEARANCE FROM EDGE OF PAD (DOOR SIDE)
4, 20 PLAN VIEW
SEC. CABLE
5RM1P AREA r.-
FINAL GRADE,
PLACE PAD ON 6' OF 3/4' CRUSHED ROCK
(SEE NOTE 3, 5, AND 6.) PRI. CABLES --� 6'
END VIEW MINI- PADMOUNT (SEE NOTE 1 AND 7.)
(FRONT) FIGURE 1
PRI. 2'
CABLES ,.'��`.�'
SEC.
CABLES FINAL GRADE
s �
STANDARD PADMOUNT /PME -2 (SEE NOTE 1.) INVERTED 17'x30'x15'
FIGURE 2 PLASTIC HANDLOE
6' OF CRUSHED ROCK (3f4' (M /C 655 - 48000)
(SEE NOTE 3 AND 5.) -- CONDUITS PER
6' CRUSHED RUCK FIGURE 1 (TYP.)
FIGURE 3
(END VIEW W /INVERTED HANDHOLE)
LO MANWACTURM NOTES,
1. Pad will be manufactured In accordance with SCE specification PCTP -9 -94 polymer
Concrete transformer and Equipment Pads' and meet all requirements for Pad 4.
2. Hold -down brackets to be P -3200 series unistrut (or equal)
2.0 INSTALLATION NOTM
1. Primary and secondary cables for min- pad - mounted transformers should be placed
Into the clear opening areas as shown in Figure 1t other transformers use Figure2. The work
order drawings will Identify which case Is required.
2. For ground rod Installation see AC 701,
3. Subgrade soil below crushed gravel Is to be mechanically compacted to 85 percent relative
compaction unless higher Is required by construction permit. Contractor is responsible for
for maintaining proper conduit location after grading.
4. Pad to be placed to proper grade relative to finished curb or other reference elevation and
level to within 1/4 Inch.
5. An Inverted handhole, as shown In figure 3, shall be Installed.
6. In known rodent problem areas, place Red! -Crete or liquid asphalt emulsion on the crushed
rock around conduits In the cable opening. Install two 1 -Inch diameter PVC pipes through
crushed rock as drains before placing Red[ -Crete and protect against becoming clogged.
7. For conduit Installation using Figure 1, a template should be used to locate conduit or CIC.
8. Service conduits shall be seated or plugged when the transformer Is located above a
customer's meter panel, per G.O. 128, Rule 31.6.
9. Riser bends shalt be schedule 40 PVC minimum on the primary side.
7/16" x 1' -10" x 5' -1" Protective
Barrier Pc '" 0.
5' -1" x 5' -1" Openii
Top Sectic
1/2"0 Grounding Inser
3 Ea. End W,
6 Toi
7/8 "0 Pull
2 Ea. End
8
Top and B<
Base
Approximate Weights
Top - 10200 Lbs
Base - 12100 Lbs
5'x10' -6 "x7' PME
/-Steel Closure Plate
14" x 10" x 1/4"
SCALE:1 /4" = 1' -0"
514" x 10'4"' x 711-0111
Cover With
ne and Gasket
106 Traffic
failable
ig Pin
mr Manhole Opening
i "b Terminators
2 Ea. End Wall
?4 Total
Overall Outside Dimensions
6' -3 1/2"W x 11' -7 1 x 8' =0 "H
Overall Inside Dimensions
5' -0"W x 10' -6 "L x 7' -0 "H
VAULT
514" x 10' -6" x 7' -0"
4' x 5' x 8" Concrete Cover
Use Felt Between Cover
4' x 5' x 12" Neck Ring
Optional Risers Are Available
and Are Positioned Between
The Vault and The Neck Ring
2 Ton Swi#tlif
2 Ea. Side W(
4 Tot
4 Ton Swiftlifts
4 Total
Top Section
1/2 "0 Grounding Inserts
3 Ea. End Walt
6 Total
4' -0"
7/8 "0 Pull Iron
2 Ea. End Wall
Top and Base
8 Total
Base Section
Approximate Weights
Top - -11500 Lbs
Base 12100 Lbs
5' -10"
SCALE:1 /4" -- 1' -0"
dentification Spot
Traffic Cover and Frame
AFCO A1106 or Equal
5 "0 Terminators
4 Ea. End Wall
8 Total
10 "o Vent
1 Ea. End Wall
2 Total
1/2 *0 i -5000 Plastic Inserts
8 Ea. Side Wall
16 Total
5 ",0 Terminators
12 Ea. End Wall
24 Total
Overall Outside Dimensions
6' -1 "W x 11'-7L x 8'-6 3/4 "H
Overall Inside Dimensions
5' -0 "W x 10' -6 "L x 7'-0 "H
BID SET 3/10/14
Pi
3--1/C 100E
sc
3 -1 /C 1000
p3 -1 / ,
C
b
z
Q C�
W
Z w
I0
U m
Q W
� W
VAULT / PICK —UP POINT ' A"
3-1/C 1000 JCN -12KV
SCALE 1 "= 40'
GROUND ASSEMBLY HOOKS AND RACKS
6- 600A ELBOW
1013'- 3 -1 /C 1000 JCN- 12KV(TO VAULT NEST)
�w
J
it
O
Z W
J m
� W
� W
m�
wW
z W
Z�
U W
~ W
Q �
BID SET 3/10/14
n
a•.
ww
zW
uw
�w
Q�
11w
J
O
J J
J m
� W
� W
(/7
5'x10'6 #x7' PME
GROUND ASSEMBLY HOOKS AND RACKS
1- PME --9CL
6-- 600A ELBOW
6- 200A INSULATED RECEPTACLE
242' - 3-1/C 1000 JCN -12KV
E
C/V
IMN r
SCALE 1 "= 40'
3/10/14