HomeMy WebLinkAbout08-41 - Resolutions RESOLUTION NO. 08-41
A RESOLUTION OF THE PLANNING COMMISSION OF THE CITY OF RANCHO
CUCAMONGA, CALIFORNIA, APPROVING DEVELOPMENT REVIEW
DRC2006-00730, THE DESIGN REVIEW OF 67 CONDOMINIUM UNITS FOR
TENTATIVE TRACT MAP SUBTT18212 IN THE MEDIUM RESIDENTIAL
DISTRICT (8-14 DWELLING UNITS PER ACRE) OF THE VICTORIA
COMMUNITY PLAN, LOCATED AT THE NORTHEAST CORNER OF
BASE LINE ROAD AND SAN CARMELA COURT, AND MAKING FINDINGS IN
SUPPORT THEREOF -APN: 1089-581-01.
A. Recitals.
1. Charles Joseph Associates, on behalf of Baseline Victoria Park Partners LLC, filed an
application for Development Review DRC2006-00730, the design review of 67 condominium units for
Tentative Tract Map SUBTT18212, as described in the title of this Resolution. Hereinafter in this
Resolution, the subject Development Review request is referred to as "the application."
2. On the 27th day of August 2008,the Planning Commission of the City of Rancho Cucamonga
held a meeting to consider the application.
3. All legal prerequisites prior to the adoption of this Resolution have occurred.
B. Resolution.
NOW, THEREFORE, it is hereby found, determined, and resolved by the Planning Commission of
the City of Rancho Cucamonga as follows:
1. This Commission hereby specifically finds that all of the facts set forth in the Recitals, Part A,of
this Resolution are true and correct.
2. Based upon the substantial evidence presented to this Commission during the
above-referenced meeting on August 27, 2008, including written and oral staff reports, this Commission
hereby specifically finds as follows:
a. The application applies to a 4.79-acre site located on the northeast corner of Base Line
Road and San Carmela Road, with a Base Line Road street frontage of approximately 320 feet; and
b. The project site is currently zoned Village Commercial and is within the Victoria
Community Plan (VCP). The properties surrounding the site are also in the VCP and specifically identified
as single-family residential development to the east and west in the Low-Medium Density Residential
District; condominiums to the north in the Medium-High Residential District; and a small commercial retail
center to the immediate south/southeast in the Village Commercial District. Further south across
Base Line Road is the Filippi Winery in the High Density Residential District; and
C. The applicant has concurrently applied for General Plan and Victoria Community Plan
land use amendments to change the current land use designations from commercial to medium density
residential; and
d. The proposed use,together with the conditions applicable thereto,will not be detrimental
to the public health, safety, or welfare or materially injurious to properties or improvements in the vicinity;
and
PLANNING COMMISSION RESOLUTION NO. 08-41
DEVELOPMENT REVIEW DRC2006-00730 — CHARLES JOSEPH ASSOCIATES
August 27, 2008
Page 2
e. The project design meets or exceeds the Victoria Community Plan development
standards for setbacks, building separations, and recreational amenities; and
f. The design and exterior materials of the condominium units includes the use of high
quality plaster(stucco), exposed rafter tails,decorative window surrounds,concrete tile roofing,decorative
block walls, wrought iron accents, and metal fencing, thereby, providing 360-degree architectural
treatment, a goal of the General Plan.
3. Based upon the substantial evidence presented to this Commission during the
above-referenced meeting and upon the specific findings of facts set forth in Paragraphs 1 and 2 above,
this Commission hereby specifically finds and concludes as follows:
a. That the proposed project is consistent with the objectives of the General Plan; and
b. That the proposed design is in accord with the objectives of the Victoria Community Plan
and the purposes of the district in which the site is located; and
C. That the proposed design is in compliance with each of the applicable provisions of the
Rancho Cucamonga Development Code; and
d. That the proposed design, together with the conditions applicable thereto, will not be
detrimental to the public health, safety, or welfare or materially injurious to properties or improvements in
the vicinity.
4. Based upon the facts and information contained in the proposed Mitigated Negative
Declaration, together with all written and oral reports included for the environmental assessment for the
application,the Planning Commission finds that there is no substantial evidence that the project will have a
significant effect upon the environment and adopts a Mitigated Negative Declaration and Mitigated
Monitoring Program attached hereto, and incorporated herein by this reference, based upon the findings
as follows:
a. Pursuant to the California Environmental Quality Act("CEQA")and the City's local CEQA
Guidelines, the City staff prepared an Initial Study of the potential environmental effects of the project.
Based on the findings contained in that Initial Study, City staff determined that, with the imposition of
mitigation measures, there would be no substantial evidence that the project would have a significant
effect on the environment. Based on that determination, a Mitigated Negative Declaration was prepared.
Thereafter,the City staff provided public notice of the public comment period and of the intent to adopt the
Mitigated Negative Declaration.
b. The Planning Commission has reviewed the Mitigated Negative Declaration and all
comments received regarding the Mitigated Negative Declaration and, based on the whole record before
it, finds: (i) that the Mitigated Negative Declaration was prepared in compliance with CEQA; and (ii) that,
based on the imposition of mitigation measures, there is no substantial evidence that the project will have
a significant effect on the environment. The Planning Commission further finds that the Mitigated Negative
Declaration reflects the independent judgment and analysis of the Planning Commission. Based on these
findings, the Planning Commission hereby adopts the Mitigated Negative Declaration.
C. The Planning Commission has also reviewed and considered the Mitigation Monitoring
Program for the project that has been prepared pursuant to the requirements of Public Resources Code
Section 21081.6 and finds that such Program is designed to ensure compliance with the mitigation
measures during project implementation. The Planning Commission therefore adopts the Mitigation
Monitoring Program for the project.
PLANNING COMMISSION RESOLUTION NO. 08-41
DEVELOPMENT REVIEW DRC2006-00730—CHARLES JOSEPH ASSOCIATES
August 27, 2008
Page 3
d. The custodian of records for the Initial Study, Mitigated Negative Declaration, Mitigation
Monitoring Program and all other materials which constitute the record of proceedings upon which the
Planning Commission's decision is based is the Planning Director of the City of Rancho Cucamonga.
Those documents are available for public review in the Planning Department of the City of Rancho
Cucamonga located at 10500 Civic Center Drive, Rancho Cucamonga, California 91730,telephone(909)
477-2750.
5. Based upon the findings and conclusions set forth in paragraphs 1, 2, 3, and 4 above, this
Commission hereby approves the application subject to each and every condition set forth below and in
the Standard Conditions, attached hereto and incorporated herein by this reference:
Planninq Department
1) This approval is for the site plan, exterior building design, and landscaping for
the 67-unit condominium project at the subject site. Plans submitted for plan
check shall conform with the plans approved by the Design Review
Committee on July 15, 2008, and final Planning Commission approval on
August 27, 2008.
2) Final project approval shall be subject to City Council approval of the
associated land use amendments of the Rancho Cucamonga General Plan
and Victoria Community Plan changing the land use from Commercial to
Medium Density Residential.
3) All guest parking spaces shall be conspicuously labeled as "Visitor" parking
and made available for visitors to the complex at all times. Sub-leasing,
sub-renting, or any other method which results in the reduction of available of
visitor parking spaces (18) shall be prohibited.
4) No exterior changes to the design of the project, including exterior materials,
shall be permitted without prior City review and approval.
5) All applicable conditions of approval for Tentative Tract Map SUBTT18212
shall apply.
6) The final design of the following items shall be submitted for final Planning
Director review and approval during the plan check phase of the project:
a) All decorative metal fences, gates, and/or railings. All decorative
exterior metal elements shall have a long lasting powder coat paint
finish.
b) Masonry walls and/or fencing between condominium units. Walls shall
be stepped as necessary to comply with field conditions and to comply
with wall requirements of the development code. No unfinished walls
shall be permitted.
c) Wall- and ground-mounted exterior light fixtures.
7) Any stone veneers used on the project (e.g., buildings, perimeter walls,
pilasters, etc.), shall be installed in a manner that does not give the
appearance of a tack on element. All stone veneers shall be applied and/or
extended so that the material terminates at an appropriate point on the
PLANNING COMMISSION RESOLUTION NO. 08-41
DEVELOPMENT REVIEW DRC2006-00730 — CHARLES JOSEPH ASSOCIATES
August 27, 2008
Page 4
structure. No faux river rock shall be permitted.
8) Tree Removal Permit DRC2007-00081 is hereby approved for the removal of
all on-site trees (approximately 49 trees)for the development of the site and
to be replaced as part of the approved landscape plan for the project.
9) No pedestrian gates with direct access to San Carmela Court shall be
permitted with this approval. Pedestrian access shall be provided directly to
Base Line Road.
10) Access from the project to San Carmela Court shall be for emergency
response vehicles/personnel only.
11) The project homeowner association shall be responsible at all times to
maintain and repair (including graffiti removal) all perimeter walls, gates,
landscaping, decorative features, and on-site recreation amenities.
12) Approval of this Development Review application is contingent on the
approval of the General Plan Amendment to change the Neighborhood
Commercial designation to Medium Residential.
Engineering Department
1) Base Line Road frontage improvements shall be in accordance with City
"Major Divided Arterial" standards as required and including:
a) Provide curb and gutter, curvilinear sidewalk, street trees and street
lights, as required.
b) For widening of Base Line Road, remove existing curb and gutter and
install new curb and gutter to its ultimate location.
c) Provide a bike lane along Base Line Road frontage as required.
d) Provide traffic striping and signage and R26 signs along Base Line
Road frontage, as required.
e) Protect existing raised median along the entire Base Line Road
frontage with no openings.
f) No direct driveways to Base Line Road.
2) San Carmela Court frontage improvements shall be in accordance with City
"collector" street standards as required and including:
a) Provide street trees, as required.
b) Protect existing curb and gutter, sidewalk, and street lights, or repair as
required.
c) Access to San Carmela Court to be limited to one Emergency Access
driveway. The emergency access shall be 26 feet wide and shall be
PLANNING COMMISSION RESOLUTION NO. 08-41
DEVELOPMENT REVIEW DRC2006-00730— CHARLES JOSEPH ASSOCIATES
August 27, 2008
Page 5
constructed as a limited access curb per City Standard 105-C. The
material to be installed within the City right-of-way shall be reviewed
and approved by the Rancho Cucamonga Fire District. No accent
paving allowed within the City right-of-way.
d) Protect existing traffic striping and signage, including R26 signs, as
required.
3) Victoria Park Lane frontage improvements shall be in accordance with City
'modified collector' standards as required and including:
a) Protect existing curb and gutter, sidewalk, street trees and street lights,
or repair as required.
b) Protect existing traffic striping and signage, including R26 signs, as
required.
c) Modify existing landscaping on Victoria Park Lane approaching Atwood
Street to comply with the City's "Line-of-Sight" standards.
4) Atwood Street frontage improvements shall be in accordance with City'Local
Street' standards as required and including:
a) Provide a 6-foot wide curb adjacent sidewalk, street trees and 5800
Lumens HPSV street lights, as required. Easement for Public sidewalks
placed outside the public right-of-way shall be dedicated to the City.
b) Protect existing curb and gutter, striping and signage, as required.
c) Gated entrance to be in accordance with City "Residential Project
Gated Entrance Design Guide" standard.
5) Install a traffic signal at the intersection of Base Line Road and San Carmela
Court. The developer shall receive credit against and reimbursement of
costs in excess of the Transportation Development Fee in conformance with
City Policy. If the developer fails to submit for said reimbursement agreement
with 6 months of the public improvements being accepted by the City, all
rights of the developer to reimbursement shall terminate.
6) The development requires installation of fiber optics conduits, vaults and
manholes per City Standard Plans 135-137 on Base Line Road. Also the
improvement plans need to show the location and limits of the conduits,
vaults and manholes with construction notes using Standard Plans 135-137.
7) The developer shall request that the City appropriately process and quitclaim
Lot "C" of Tract 16128 prior to final map approval. Said Lot "C" and the
adjacent parkway shall be incorporated into the development.
Environmental Mitigation
Air Quality
1) All construction equipment shall be maintained in good operating condition so
as to reduce operational emissions. The contractor shall ensure that all
PLANNING COMMISSION RESOLUTION NO. 08-41
DEVELOPMENT REVIEW DRC2006-00730— CHARLES JOSEPH ASSOCIATES
August 27, 2008
Page 6
construction equipment is being properly serviced and maintained as per
manufacturers'specifications. Maintenance records shall be available at the
construction site for City verification.
2) Prior to the issuance of any Grading Permits, the developer shall submit
Construction Plans to the City denoting the proposed schedule and projected
equipment use. Construction contractors shall provide evidence that
low-emission mobile construction equipment will be utilized, or that their use
was investigated and found to be infeasible for the project. Contractors shall
also conform to any construction measures imposed by the South Coast Air
Quality Management District (SCAQMD) as well as City Planning Staff.
3) All paints and coatings shall meet or exceed performance standards noted in
SCAQMD Rule 1113. Paints and coatings shall be applied either by hand or
high-volume, low-pressure spray.
4) All asphalt shall meet or exceed performance standards noted in SCAQMD
Rule 1108.
5) All construction equipment shall comply with SCAQMD Rules 402 and 403.
Additionally, contractors shall include the following provisions:
• Reestablish ground cover on the construction site through seeding and
watering.
• Pave or apply gravel to any on-site haul roads.
• Phase grading to prevent the susceptibility of large areas to erosion
over extended periods of time.
• Schedule activities to minimize the amounts of exposed excavated soil
during and after the end of work periods.
• Dispose of surplus excavated material in accordance with local
ordinances and use sound engineering practices.
• Sweep streets according to a schedule established by the City if silt is
carried over to adjacent public thoroughfares or occur as a result of
hauling. Timing may vary depending upon the time of year of
construction.
• Suspend grading operations during high winds (i.e., wind speeds
exceeding 25 mph) in accordance with Rule 403 requirements.
• Maintain a minimum 24-inch freeboard ratio on soils haul trucks or
cover payloads using tarps or other suitable means.
6) The site shall be treated with water or other soil-stabilizing agent (approved
by SCAQMD and Regional Water Quality Control Board [RWQCB]) daily to
reduce PM10 emissions, in accordance with SCAQMD Rule 403.
PLANNING COMMISSION RESOLUTION NO. 08-41
DEVELOPMENT REVIEW DRC2006-00730 — CHARLES JOSEPH ASSOCIATES
August 27, 2008
Page 7
7) Chemical soil-stabilizers (approved by SCAQMD and RWQCB) shall be
applied to all inactive construction areas that remain inactive for 96 hours or
more to reduce PM10 emissions.
8) The construction contractor shall utilize electric or clean alternative
fuel-powered equipment where feasible.
9) The construction contractor shall ensure that Construction Grading Plans
include a statement that work crews will shut off equipment when not in use.
10) All residential and commercial structures shall be required to incorporate
high-efficiency/low-polluting heating, air conditioning, appliances, and water
heaters.
11) All residential and commercial structures shall be required to incorporate
thermal pane windows and weather-stripping.
Cultural Resources
1) If any prehistoric archaeological resources are encountered before or during
grading, the developer will retain a qualified archaeologist to monitor
construction activities, to take appropriate measures to protect or preserve
them for study. With the assistance of the archaeologist, the City of Rancho
Cucamonga will:
• Enact interim measures to protect undesignated sites from demolition
or significant modification without an opportunity for the Cityto establish
its archaeological value.
• Consider establishing provisions to require incorporation of
archaeological sites within new developments, using their special
qualities as a theme or focal point.
• Pursue educating the public about the area's archaeological heritage.
• Propose mitigation measures and recommend conditions of approval to
eliminate adverse project effects on significant, important, and unique
prehistoric resources, following appropriate CEQA guidelines.
• Prepare a technical resources management report, documenting the
inventory, evaluation, and proposed mitigation of resources within the
project area. Submit one copy of the completed report with original
illustrations, to the San Bernardino County Archaeological Information
Center for permanent archiving.
2) If any paleontological resource (i.e. plant or animal fossils) are encountered
before or during grading, the developer will retain a qualified paleontologist to
monitor construction activities, to take appropriate measures to protect or
preserve them for study. The paleontologist shall submit a report of findings
that will also provide specific recommendations regarding further mitigation
measures (i.e., paleontological monitoring)that may be appropriate. Where
mitigation monitoring is appropriate, the program must include, but not be
limited to, the following measures:
PLANNING COMMISSION RESOLUTION NO. 08-41
DEVELOPMENT REVIEW DRC2006-00730— CHARLES JOSEPH ASSOCIATES
August 27, 2008
Page 8
• Assign a paleontological monitor, trained and equipped to allow the
rapid removal of fossils with minimal construction delay, to the site
full-time during the interval of earth-disturbing activities.
• Should fossils be found within an area being cleared or graded, divert
earth-disturbing activities elsewhere until the monitor has completed
salvage. If construction personnel make the discovery, the grading
contractor should immediately divert construction and notify the monitor
of the find.
• Prepare, identify, and curate all recovered fossils for documentation in
the summary report and transfer to an appropriate depository
(i.e., San Bernardino County Museum).
• Submit a summary report to the City of Rancho Cucamonga. Transfer
collected specimens with a copy of the report to San Bernardino County
Museum.
Geology and Soils
1) The site shall be treated with water or other soil-stabilizing agent (approved
by SCAQMD and RWQCB) daily to reduce PM10 emissions, in accordance
with SCAQMD Rule 403 or re-planted with drought resistant landscaping as
soon as possible.
2) Frontage public streets shall be swept according to a schedule established by
the City to reduce PM10 emissions associated with vehicle tracking of soil
off-site. Timing may vary depending upon the time of year of construction.
3) Grading operations shall be suspended when wind speeds exceed 25 mph to
minimize PM10 emissions from the site during such episodes.
4) Chemical soil-stabilizers (approved by SCAQMD and RWQCB) shall be
applied to all inactive construction areas that remain inactive for 96 hours or
more to reduce PM10 emissions.
Hydrology and Water Quality
1) Prior to issuance of grading permits, the permit applicant shall submit to
Building Official for approval a Storm Water Pollution Prevention Plan
(SWPPP) specifically identifying Best Management Practices (BMPs) that
shall be used on-site to reduce pollutants during construction activities
entering the storm drain system to the maximum extent practical.
2) An Erosion Control Plan shall be prepared, included in the Grading Plan,and
implemented for the proposed project that identifies specific measures to
control on-site and off-site erosion from the time of ground disturbing
activities are initiated through completion of grading. This Erosion Control
Plan shall include the following measures at a minimum: a) Specify the
timing of grading and construction to minimize soil exposure to rainy periods
experienced in southern California, and b) An inspection and maintenance
program shall be included to ensure that any erosion which does occur either
on-site or off-site as a result of this project will be corrected through a
PLANNING COMMISSION RESOLUTION NO. 08-41
DEVELOPMENT REVIEW DRC2006-00730— CHARLES JOSEPH ASSOCIATES
August 27, 2008
Page 9
remediation or restoration program within a specified time frame.
3) During construction,temporary berms such as sandbags or gravel dikes must
be used to prevent discharge of debris or sediment from the site when there
is rainfall or other runoff.
4) During construction, to remove pollutants, street cleaning will be performed
prior to storm events and after the use of water trucks to control dust in order
to prevent discharge of debris or sediment from the site.
5) The developer shall implement the BMPs identified in the Water Quality
Management Plan (WQMP) prepared by R.T. Quinn &Associates (May 14,
2008)to reduce pollutants after construction entering the storm drain system
to the maximum extent practical.
6) Landscaping plans shall include provisions for controlling and minimizing the
use of fertilizers/pesticides/herbicides. Landscaped areas shall be monitored
and maintained for at least two years to ensure adequate coverage and
stable growth. Plans for these areas, including monitoring provisions for a
minimum of two years, shall be submitted to the City for review and approval
prior to the issuance of grading permits.
7) Prior to issuance of building permits, the applicant shall submit to the City
Engineer for approval of a WQMP, including a project description and
identifying BMPs that will be used on-site to reduce pollutants into the storm
drain system to the maximum extent practicable. The WQMP shall identify
the structural and non-structural measures consistent with the Guidelines for
New Development and Redevelopment adopted by the City of
Rancho Cucamonga in June 2004.
8) Prior to issuance of grading or paving permits, the applicant shall obtain a
Notice of Intent (NOI) to comply with obtaining coverage under the National
Pollutant Discharge Elimination System (NPDES) General Construction
Storm Water Permit from the State Water Resources Control Board.
Evidence that this has been obtained (i.e., a copy of the Waste Discharger's
Identification Number) shall be submitted to the City Building Official for
coverage under the NPDES General Construction Permit.
Noise
1) Prior to issuance of Building Permits, the applicant shall submit to the
Planning Director and Building Official for review and approval, building plans
that demonstrate compliance with the noise attenuation recommendations of
the acoustical engineer as contained in the Noise Impact Analysis prepared
by LSA Associates(August 2006), and on file with the Planning Department.
Any alternative methods proposed for mitigating noise impacts on the project
shall be prepared by the acoustical engineer and presented to the City for
review and approval by the Planning and Building Departments.
2) Construction or grading on weekdays shall not take place between the hours
of 8:00 p.m. and 6:30 a.m., including Saturday, or at any time on Sunday or a
national holiday.
PLANNING COMMISSION RESOLUTION NO. 08-41
DEVELOPMENT REVIEW DRC2006-00730— CHARLES JOSEPH ASSOCIATES
August 27, 2008
Page 10
3) Construction or grading noise levels shall not exceed the standards specified
in Development Code Section 17.02.120-D,as measured at the property line.
The developer shall hire a consultant to perform weekly noise level
monitoring as specified in Development Code Section 17.02.120. Monitoring
at other times may be required by the Building Official. Said consultant shall
report their findings to the Building Official within 24 hours; however, if noise
levels exceed the above standards, then the consultant shall immediately
notify the Building Official. If noise levels exceed the above standards, then
construction activities shall be reduced in intensity to a level of compliance
with above noise standards or halted.
4) The perimeter block wall shall be constructed as early as possible in first
phase.
5) Haul truck deliveries on weekdays shall not take place between the hours of
8:00 p.m. and 6:30 a.m. including Saturday, or at any time on Sunday or a
national holiday. Additionally, if heavy trucks used for hauling would exceed
100 daily trips (counting both to and from the construction site), then the
developer shall prepare a Noise Mitigation Plan denoting any construction
traffic haul routes. To the extent feasible, the plan shall denote haul routes
that do not pass sensitive land uses or residential dwellings.
6. The Secretary to this Commission shall certify to the adoption of this Resolution.
APPROVED AND ADOPTED THIS 27TH DAY OF AUGUST 2008.
PLANNING COMMISSION OF THE CITY OF RANCHO CUCAMONGA
BY:
Richard B. Fletcher, Chairman
ATTEST: r/
JarrWs R. Troyer, AICP, Secretary
I, James R. Troyer, AICP, Secretary of the Planning Commission of the City of Rancho Cucamonga, do
hereby certify that the foregoing Resolution was duly and regularly introduced, passed,and adopted by the
Planning Commission of the City of Rancho Cucamonga, at a regular meeting of the Planning
Commission held on the 27th day of August 2008, by the following vote-to-wit:
AYES: COMMISSIONERS: FLETCHER, HOWDYSHELL, MUNOZ, STEWART, WIMBERLY
NOES: COMMISSIONERS: NOME
ABSENT: COMMISSIONERS: NONE
City of Rancho Cucamonga
in MITIGATION MONITORING
PROGRAM
Project File No.: Victoria Community Plan Amendment DRC2006-00447, General Plan
Amendment Plan DRC2006-00224,Tentative Tract Map SUBTT18212, and Development Review
DRC2006-00730.
This Mitigation Monitoring Program (MMP)has been prepared for use in implementing the mitigation
measures identified in the Mitigated Negative Declaration)for the above-listed project. This program
has been prepared in compliance with State law to ensure that adopted mitigation measures are
implemented (Section 21081.6 of the Public Resources Code).
Program Components - This MMP contains the following elements:
1. Conditions of approval that act as impact mitigation measures are recorded with the action
and the procedure necessary to ensure compliance. The mitigation measure conditions of
approval are contained in the adopted Resolution of Approval for the project.
2. A procedure of compliance and verification has been outlined for each action necessary. This
procedure designates who will take action, what action will be taken and when, and to whom
and when compliance will be reported.
3. The MMP has been designed to provide focused, yet flexible guidelines. As monitoring
progresses, changes to compliance procedures may be necessary based upon
recommendations by those responsible for the program.
Program Management- The MMP will be in place through all phases of the project. The project
planner, assigned by the Planning Director, shall coordinate enforcement of the MMP. The project
planner oversees the MMP and reviews the Reporting Forms to ensure they are filled out correctly
and proper action is taken on each mitigation. Each City department shall ensure compliance of the
conditions (mitigation) that relate to that department.
Procedures -The following steps will be followed by the City of Rancho Cucamonga.
1. A fee covering all costs and expenses, including any consultants'fees, incurred by the City in
performing monitoring or reporting programs shall be charged to the applicant.
2. A MMP Reporting Form will be prepared for each potentially significant impact and its
corresponding mitigation measure identified in the Mitigation Monitoring Checklist, attached
hereto. This procedure designates who will take action, what action will be taken and when,
and to whom and when compliance will be reported. All monitoring and reporting
documentation will be kept in the project file with the department having the original authority
for processing the project. Reports will be available from the City upon request at the following
address:
City of Rancho Cucamonga— Lead Agency
Planning Department
10500 Civic Center Drive
Rancho Cucamonga, CA 91730
MITIGATION MONITORING PROGRAM
DRC2006-00447, DRC2006-00224, SUBTT18212, AND DRC2006-00730
August 27, 2008
Page 2
3. Appropriate specialists will be retained if technical expertise beyond the City staff's is needed,
as determined by the project planner or responsible City department, to monitor specific
mitigation activities and provide appropriate written approvals to the project planner.
4. The project planner or responsible City department will approve, by signature and date, the
completion of each action item that was identified on the MMP Reporting Form. After each
measure is verified for compliance, no further action is required for the specific phase of
development.
5. All MMP Reporting Forms for an impact issue requiring no further monitoring will be signed off
as completed by the project planner or responsible City department at the bottom of the MMP
Reporting Form.
6. Unanticipated circumstances may arise requiring the refinement or addition of mitigation
measures. The project planner is responsible for approving any such refinements or
additions. An MMP Reporting Form will be completed by the project planner or responsible
City department and a copy provided to the appropriate design, construction,or operational
personnel.
7. The project planner or responsible City department has the authority to stop the work of
construction contractors if compliance with any aspects of the MMP is not occurring after
written notification has been issued. The project planner or responsible City department also
has the authority to hold certificates of occupancies if compliance with a mitigation measure
attached hereto is not occurring. The project planner or responsible City department has the
authority to hold issuance of a business license until all mitigation measures are implemented.
8. Any conditions (mitigation) that require monitoring after project completion shall be the
responsibility of the City of Rancho Cucamonga Planning Department. The Department shall
require the applicant to post any necessary funds (or other forms of guarantee)with the City.
These funds shall be used by the City to retain consultants and/or pay for City staff time to
monitor and report on the mitigation measure for the required period of time.
9. In those instances requiring long-term project monitoring, the applicant shall provide the City
with a plan for monitoring the mitigation activities at the project site and reporting the
monitoring results to the City. Said plan shall identify the reporter as an individual qualified to
know whether the particular mitigation measure has been implemented. The
monitoring/reporting plan shall conform to the City's MMP and shall be approved by the
Community Development Director or Planning Director prior to the issuance of building
permits.
MITIGATION MONITORING CHECKLIST (INITIAL STUDY PART III)
Project File No.: DRC2006-00447 DRC2006-00224 SUBTT18212 and DRC2006.00730
Applicant: Cal Coast Homes - Charles Joseph and Associates
Initial Study Prepared by: Steve Fowler Date: July 30. 2008
MethodMitigation Measures No. Responsible Monitoring Timing of of Verified Sanctions for
Implementing Action for Monitoring Frequency Verification Verification Date linitials Non-Compliance
Air Quality
All construction equipment shall be maintained in good PD C Review of plans A/C 2/4
operating condition so as to reduce operational
emissions. The contractor shall ensure that all
construction equipment is being properly serviced and
maintained as per manufacturers' specifications.
Maintenance records shall be available at the
construction site for City verification.
Prior to the issuance of any Grading Permits, the PD/130 C Review of plans C 2
developer shall submit Construction Plans to the City
denoting the proposed schedule and projected
equipment use. Construction contractors shall provide
evidence that low-emission mobile construction
equipment will be utilized, or that their use was
investigated and found to be infeasible for the project.
Contractors shall also conform to any construction
measures imposed by the South Coast Air Quality
Management District(SCAQMD) as well as City Planning
staff.
All paints and coatings shall meet or exceed PD C Review of plans A/C 2/4
performance standards noted in SCAQMD Rule 1113.
Paints and coatings shall be applied either by hand or
high-volume, low-pressure spray.
All asphalt shall meet or exceed performance standards BO B Review of plans A/C 2
noted in SCAQMD Rule 1108.
1 of 8
Mitigation Measures
• ResponsibleMonitoring 1 1 Method • • 1 1
Implementing • •r Monitoring Frequency Verification1n Date/initials Non-Comp
All construction equipment shall comply with SCAQMD BO C Review of plans A/C 2/4
Rules 402 and 403. Additionally, contractors shall
include the following provisions:
• Reestablish ground cover on the construction site BO C Review of plans A/C 2/4
through seeding and watering.
• Pave or apply gravel to any on-site haul roads. BO C Review of plans A/C 2/4
• Phase grading to prevent the susceptibility of large BO C Review of plans A/C 2/4
areas to erosion over extended periods of time.
• Schedule activities to minimize the amounts of BO C Review of plans A/C 2/4
exposed excavated soil during and after the end of
work periods.
• Dispose of surplus excavated material in accordance BO C Review of plans A 4
with local ordinances and use sound engineering
practices.
• Sweep streets according to a schedule established BO C During A 4
by the City if silt is carried over to adjacent public construction
thoroughfares or occurs as a result of hauling.
Timing may vary depending upon the time of year of
construction.
• Suspend grading operations during high winds(.e., BO C During A 4
wind speeds exceeding 25 mph)in accordance with construction
SCAQMD Rule 403 requirements.
• Maintain a minimum 24-inch freeboard ratio on soils BO C During A 4
haul trucks or cover payloads using tarps or other Construction
suitable means.
The site shall be treated with water or other BO C During A 4
soil-stabilizing agent (approved by SCAQMD and construction
Regional Water Quality Control Board[RWQCBj)dailyto
reduce PM10 emissions, in accordance with SCAQMD
Rule 403.
Chemical soil-stabilizers (approved by SCAQMD and BO C During A 4
RWQCB) shall be applied to all inactive construction construction
areas that remain inactive for 96 hours ormoreto reduce
PMIO emissions.
2of8
Mitigation Measures No. Responsible Monitoring Timing of Method of
Implementing Action for Monitoring Frequency Verification Verification Date /initials Non-Compliance
The construction contractor shall utilize electric or clean BO C Review of plans A/C 4
alternative fuel-powered equipment where feasible.
The construction contractor shall ensure that BO C Review of plans A/C 2/4
Construction Grading Plans include a statement that
work crews will shut off equipment when not in use.
All residential and commercial structures shall be BO C/D Review of plans C 2/4
required to incorporate high-efficiency/low-polluting
heating,air conditioning,appliances,and water heaters.
All residential and commercial structures shall be BO C/D Review of plans C 2/4
required to incorporate thermal pane windows and
weather-stripping.
Cultural Resources
If any prehistoric archaeological resources are
encountered before orduring grading,the developerwill
retain a qualified archaeologist to monitor construction
activities, to take appropriate measures to protect or
preserve them for study. With the assistance of the
archaeologist,the City of Rancho Cucamonga will:
• Enact interim measures to protect undesignated sites PD/BO C Review of report A/D 3/4
from demolition or significant modification without an
opportunity for the City to establish its archaeological
value.
• Consider establishing provisions to require PD/BO C Review of report A/D 3/4
incorporation of archaeological sites within new
developments, using their special qualities as a
theme or focal point.
• Pursue educating the public about the area's PD/BO C Review of report A/D 3/4
archaeological heritage.
• Propose mitigation measures and recommend PD/BO C Review of report A/D 3/4
conditions of approval to eliminate adverse project
effects on significant, important, and unique
prehistoric resources, following appropriate CEQA
guidelines.
3of8
Mitigation Measures No. Responsible , of Method .
Implementing Action for Monitoring Frequency Verification Verification Date/Initials Non-Compliance
• Prepare a technical resources management report, PD C Review of report A/D 3/4
documenting the inventory,evaluation,and proposed
mitigation of resources within the project area.
Submit one copy of the completed report, with
original illustrations, to the San Bernardino County
Archaeological Information Center for permanent
archiving.
If any paleontological resource (i.e. plant or animal PD B Review of report AID 4
fossils) are encountered before or during grading, the
developer will retain a qualified paleontologist to monitor
construction activities, to take appropriate measures to
protect or preserve them for study. The paleontologist
shall submit a report of findings that will also provide
specific recommendations regarding further mitigation
measures (i.e., paleontological monitoring) that may be
appropriate. Where mitigation monitoring is appropriate,
the program must include, but not be limited to, the
following measures:
• Assign a paleontological monitor, trained and PD B Review of report A/D 4
equipped to allow the rapid removal of fossils with
minimal construction delay,to the site full-time during
the interval of earth-disturbing activities.
• Should fossils be found within an area being cleared PD/BO B/C Review of report A/D 4
or graded,divert earth-disturbing activities elsewhere
until the monitor has completed salvage. If
construction personnel make the discovery, the
grading contractor should immediately divert
construction and notify the monitor of the find.
• Prepare,identify,and curate all recovered fossils for PD D Review of report D 3
documentation in the summary report and transferto
an appropriate depository (i.e., San Bernardino
County Museum).
• Submit a summary report to the City of Rancho PD D Review of report D 3
Cucamonga. Transfer collected specimens with a
copy of the report to San Bernardino County
Museum.
4of8
Mitigation Implementing 1 Responsible Monitoring I t Method 1
Measures 1 1 Monitoring FrequencyNon-Compliance
Geology and Soils
The site shall be treated with water or other BO C During A 4
soil-stabilizing agent (approved by SCAQMD and construction
RWQCB)daily to reduce PM10 emissions,in accordance
with SCAQMD Rule 403 or re-planted with drought
resistant landscaping as soon as possible.
Frontage public streets shall be swept according to a BO C During A 4
schedule established by the City to reduce PM10 construction
emissions associated with vehicle tracking of soil off-site.
Timing may vary depending upon the time of year of
construction.
Grading operations shall be suspended when wind BO C During A 4
speeds exceed 25 mph to minimize PM10 emissions from construction
the site during such episodes.
Chemical soil-stabilizers (approved by SCAQMD and BO C During A 4
RWQCB) shall be applied to all inactive construction construction
areas that remain inactive for 96 hours or more to reduce
PM10 emissions.
Hydrology and Water Quality
Prior to issuance of grading permits,the permit applicant BO B/C/D Review of plans A/C 2/4
shall submit to the Building Official for approval a Storm
Water Pollution Prevention Plan (SWPPP) specifically
identifying Best Management Practices(BMPs)that shall
be used on-site to reduce pollutants during construction
activities entering the storm drain system to the
maximum extent practical.
5of8
Mitigation Measures No. Responsible Monitoring Timing of Method of Verified Sanctions for
Implementing Action for Monitoring Frequency Verification Verification Date/Initials Non-Compliance
An Erosion Control Plan shall be prepared, included in BO B/C/D Review of plans A/C 2/4
the Grading Plan, and implemented for the proposed
project that identifies specific measures to control on-site
and off-site erosion from the time of ground disturbing
activities are initiated through completion of grading. This
Erosion Control Plan shall include the following
measures at a minimum: a)Specify the timing of grading
and construction to minimize soil exposure to rainy
periods experienced in southern California, and b) An
inspection and maintenance program shall be included
to ensure that any erosion which does occur either on-
site or off-site as a result of this project will be corrected
through a remediation or restoration program within a
specified time frame.
During construction,temporary berms such assandbags BO B/C/D Review of plans A/C 2/4
or gravel dikes must be used to prevent discharge of
debris or sediment from the site when there is rainfall or
other runoff.
During construction,to remove pollutants,street cleaning BO B/C/D Review of plans A/C 2/4
will be performed prior to storm events and after the use
of water trucks to control dust in order to prevent
discharge of debris or sediment from the site.
The developer shall implement the BMPs identified in the CE B/C/D Review of plans A/C 2/4
Water Quality Management Plan (WQMP) prepared by
R.T. Quinn & Associates (May 14, 2008) to reduce
pollutants after construction entering the storm drain
system to the maximum extent practical.
Landscaping plans shall include provisions for controlling BO B/C/D Review of plans A/C 2/4
and minimizing the use of fertilizers/pesticides/herbicides.
Landscaped areas shall be monitored and maintained
for at least two years to ensure adequate coverage and
stable growth. Plans for these areas, including
monitoring provisions for a minimum of two years,shall
be submitted to the City for review and approval prior to
the issuance of grading permits.
6of8
Mitigation Measures No. Responsible Monitoring Timing of Method of Verified Sanctions for
Implementing Action for Monitoring Frequency Verification Verification Date /initials Non-Compliance
Prior to the issuance of building permits, the applicant CE B/CJD Review of plans A/C 2/4
shall submit to the City Engineer for approval of a
WQMP, including a project description and identifying
BMPs,that will be used on-site to reduce pollutants into
the storm drain system to the maximum extent
practicable. The WQMP shall identify the structural and
non-structural measures consistent with the Guidelines
for New Development and Redevelopment adopted by
the City of Rancho Cucamonga in June 2004.
Prior to the issuance of grading or paving permits, the BO B/C/D Review of plans A/C 2/4
applicant shall obtain a Notice of Intent(NOI)to comply
with obtaining coverage under the National Pollutant
Discharge Elimination System (NPDES) General
Construction Storm Water Permit from the State Water
Resources Control Board. Evidence that this has been
obtained (i.e., a copy of the Waste Discharger's
Identification Number) shall be submitted to the City
Building Official for coverage under the NPDES General
Construction Permit.
Noise
Prior to the issuance of building permits, the applicant PD/BO B Plan Check and C 3/4
shall submitto the Planning Director and Building Official during
for review and approval building plans that demonstrate construction
compliance with the noise attenuation recommendations
of the acoustical engineer as contained in the Noise
Impact Analysis prepared by LSA Associates
(August 2006),and on-file with the Planning Department.
Any alternative methods proposed for mitigating noise
impacts on the project shall be prepared by the
acoustical engineer and presented to the City for review
and approval by the Planning and Building Departments.
Construction or grading shall not take place between the BO C During A 4
hours of 8:00 p.m.and 6:30 a.m.on weekdays,including construction
Saturday,or at anytime on Sunday or a national holiday.
7 of 8
Mitigation g of Method .
Implementing Action for Monitoring Frequency Verification Verification Date linitials Non-Compliance
Construction or grading noise levels shall not exceed the BO C During A 4
standards specified in Development Cade Section construction
17.02.120-D, as measured at the property line. The
developer shall hire a consultant to perform weekly noise
level monitoring as specified in Development Code
Section 17.02.120. Monitoring at other times may be
required by the Building Official. Said consultant shall
report their findings to the Building Official within
24 hours; however, if noise levels exceed the above
standards, then the consultant shall immediately notify
the Building Offical. If noise levels exceed the above
standards,then construction activities shall be reduced in
intensity to a level of compliance with above noise
standards or halted.
The perimeter block wall shall be constructed as early as PD C During A A
possible in the first phase. construction
Haul truck deliveries shall not take place between the PO/BO C During A 4/7
hours of 8:00 p.m.and 6:30 a.m.on weekdays,including construction
Saturday,or at any time on Sunday or a national holiday.
Additionally, if heavy trucks used for hauling would
exceed 100 daily trips (counting both to and from the
construction site), then the developer shall prepare a
Noise Mitigation Plan denoting any construction traffic
haul routes. To the extent feasible,the plan shall denote
haul routes that do not pass sensitive land uses or
residential dwellings.
Key to Checklist Abbreviations
Responsible Person Monitoring Frequency Method of Verification Sanctions
CDD-Community Development Director or designee A-With Each New Development A-On-site Inspection t -Withhold Recordation of Final Map
PD—Planning Director or designee B-Prior To Construction B-Other Agency Permit/Approval 2-Withhold Grading or Building Permit
CE-City Engineer or designee C-Throughout Construction C-Plan Check 3-Withhold Certificate of Occupancy
BO-Building Official or designee D-On Completion D-Separate Submittal(Reports/Studies/Plans) 4-Stop Work Order
PO-Police Captain or designee E-Operating 5-Retain Deposit or Bonds
FC-Fire Chief or designee8-Revoke CUP
7-Citation
8 of 8
COMMUNITY DEVELOPMENT
DEPARTMENT
STANDARD CONDITIONS
PROJECT #: DEVELOPMENT REVIEW DRC2006-00730
SUBJECT: DEVELOPMENT OF 67 MARKET RATE CONDOMINIUM UNITS.
APPLICANT: CHARLES JOSEPH ASSOCIATES,ON BEHALF OF BASELINE VICTORIA PARK PARTNERS LLC
LOCATION: 4.79 ACRES OF LAND AT THE NORTHEAST CORNER OF BASE LINE ROAD AND
SAN CARMELA COURT - APN: 1089-581-01.
ALL OF THE FOLLOWING CONDITIONS APPLY TO YOUR PROJECT.
APPLICANT SHALL CONTACT THE PLANNING DEPARTMENT, (909) 477-2750, FOR
COMPLIANCE WITH THE FOLLOWING CONDITIONS:
Completion Date
A. General Requirements
1. The applicant shall agree to defend at his sole expense any action brought against the City, its
agents, officers,or employees, because of the issuance of such approval,or in the alternative,to
relinquish such approval. The applicant shall reimburse the City, its agents, officers, or
employees, for any Court costs and attorney's fees which the City, its agents, officers, or
employees may be required by a court to pay as a result of such action. The City may, at its sole
discretion, participate at its own expense in the defense of any such action but such participation
shall not relieve applicant of his obligations under this condition.
2. Copies of the signed Planning Commission Resolution of Approval No. 08-41, Standard
Conditions, and all environmental mitigations shall be included on the plans (full size). The
sheet(s) are for information only to all parties involved in the construction/grading activities and
are not required to be wet sealed/stamped by a licensed Engineer/Architect.
3. The applicant shall be required to pay any applicable Fish and Game fees as shown below. The
project planner will confirm which fees apply to this project. All checks are to be made payable to
the Clerk of the Board of Supervisors and submitted to the Planning Commission Secretary prior
to the Planning Commission or Planning Director hearing:
a) Notice of Exemption -$50
b) Notice of Determination -$50
c) Negative Declaration - $ 1,926.75 X
d) Environmental Impact Report-$2,550
SC-1-05 1
hPLANNINGTINAUPLNGCOMMt2008 Res&Stf repORC2006-00730SWCond 8-27.doc
Project No.DRC2006-00730
Completion Date
B. Time Limits
1. This tentative tract map or tentative parcel map shall expire, unless extended by the Planning
Commission, unless a complete final map is filed with the City Engineer within 3 years from the
date of the approval.
2. Development/Design Review approval shall expire if building permits are not issued or approved
use has not commenced within 5 years from the date of approval. No extensions are allowed.
C. Site Development
1. The site shall be developed and maintained in accordance with the approved plans which include
site plans,architectural elevations,exterior materials and colors,landscaping,sign program,and
grading on file in the Planning Department,the conditions contained herein, Development Code
regulations, and the Victoria Community Plan.
2. Prior to any use of the project site or business activity being commenced thereon,all Conditions
of Approval shall be completed to the satisfaction of the Planning Director.
3. Occupancy of the facilities shall not commence until such time as all Uniform Building Code and
State Fire Marshal regulations have been complied with. Prior to occupancy, plans shall be
submitted to the Rancho Cucamonga Fire Protection District and the Building and Safety
Department to show compliance. The buildings shall be inspected for compliance prior to
occupancy.
4. Revised site plans and building elevations incorporating all Conditions of Approval shall be
submitted for Planning Director review and approval prior to the issuance of building permits.
5. All site, grading, landscape, irrigation, and street improvement plans shall be coordinated for
consistency prior to issuance of any permits (such as grading, tree removal, encroachment,
building, etc.) or prior to final map approval in the case of a custom lot subdivision, or approved
use has commenced, whichever comes first.
6. Approval of this request shall not waive compliance with all sections of the Development Code,all
other applicable City Ordinances, and applicable Community or Specific Plans in effect at the
time of building permit issuance.
7. A detailed on-site lighting plan, including a photometric diagram,shall be reviewed and approved
by the Planning Director and Police Department (477-2800) prior to the issuance of building
permits. Such plan shall indicate style, illumination, location, height,and method of shielding so
as not to adversely affect adjacent properties.
8. If no centralized trash receptacles are provided,all trash pick-up shall be for individual units with
all receptacles shielded from public view.
9. Trash receptacle(s)are required and shall meet City standards. The final design, locations,and
the number of trash receptacles shall be subject to Planning Director review and approval prior to
the issuance of building permits.
10. All ground-mounted utility appurtenances such as transformers, AC condensers, etc., shall be
located out of public view and adequately screened through the use of a combination of concrete
or masonry walls, berming, and/or landscaping to the satisfaction of the Planning Director. For
single-family residential developments, transformers shall be placed in underground vaults.
11. Street names shall be submitted for Planning Director review and approval in accordance with the
adopted Street Naming Policy prior to approval of the final map. '
12. All building numbers and individual units shall be identified in a clear and concise manner,
including proper illumination.
2
Project No.DRC2006-00730
Completion Date
13. The Covenants, Conditions, and Restrictions (CC&Rs) and Articles of Incorporation of the
Homeowners' Association are subject to the approval of the Planning and Engineering
Departments and the City Attorney. They shall be recorded concurrently with the Final Map or
prior to the issuance of building permits, whichever occurs first. A recorded copy shall be
provided to the City Engineer. The Homeowners' Association shall submit to the Planning
Department a list of the name and address of their officers on or before January 1 of each and
every year and whenever said information changes.
14. All parkways, open areas, and landscaping shall be permanently maintained by the property
owner,homeowners'association,or other means acceptable to the City. Proof of this landscape
maintenance shall be submitted for Planning Director and City Engineer review and approved
prior to the issuance of building permits.
15. The developer shall submit a construction access plan and schedule for the development of all
lots for Planning Director and City Engineer approval; including, but not limited to, public notice
requirements,special street posting, phone listing for community concerns,hours of construction
activity, dust control measures, and security fencing.
16. Six-foot decorative block walls shall be constructed along the project perimeter. If a double wall
condition would result, the developer shall make a good faith effort to work with the adjoining
property owners to provide a single wall. Developer shall notify, by mail,all contiguous property
owner at least 30 days prior to the removal of any existing walls/ fences along the project's
perimeter.
17. Access gates to the rear yards shall be constructed from a material more durable than wood
gates. Acceptable materials include, but are not limited to, wrought iron and PVC.
18. For residential development, return walls and corner side walls shall be decorative masonry.
19. Wood fencing shall be treated with stain, paint, or water sealant.
20. Where rock cobble is used, it shall be real river rock. Other stone veneers may be manufactured
products.
D. Building Design
1. All dwellings shall have the front,side and rear elevations upgraded with architectural treatment,
detailing and increased delineation of surface treatment subject to Planning Director review and
approval prior to issuance of building permits.
2. All roof appurtenances, including air conditioners and other roof mounted equipment and/or
projections, shall be shielded from view and the sound buffered from adjacent properties and
streets as required by the Planning Department. Such screening shall be architecturally
integrated with the building design and constructed to the satisfaction of the Planning Director.
Details shall be included in building plans.
E. Parking and Vehicular Access (indicate details on building plans)
1. All parking spaces shall be 9 feet wide by 18 feet long. When a side of any parking space abuts
a building, wall, support column, or other obstruction, the space shall be a minimum of 11 feet
wide.
2. All parking lot landscape islands shall have a minimum outside dimension of 6 feet and shall
contain a 12-inch walk adjacent to the parking stall (including curb).
3. Textured pedestrian pathways and textured pavement across circulation aisles shall be provided
throughout the development to connect dwellings/units/buildings with open spaces/plazas/
recreational uses.
3
Project No.DRC2006-00730
Completion Date
4. All parking spaces shall be double striped per City standards and all driveway aisles,entrances,
and exits shall be striped per City standards.
5. All units shall be provided with garage door openers if driveways are less than 18 feet in depth
from back of sidewalk.
6. The Covenants,Conditions and Restrictions shall restrict the storage of recreational vehicles on
this site unless they are the principal source of transportation for the owner and prohibit parking
on interior circulation aisles other than in designated visitor parking areas.
7. Plans for any security gates shall be submitted for the Planning Director, City Engineer, and
Rancho Cucamonga Fire Protection District review and approval prior to issuance of building
permits. For residential development, private gated entrances shall provide adequate turn-
around space in front of the gate and a separate visitor lane with call box to avoid cars stacking
into the public right-of-way.
F. Trip Reduction
1. Bicycle storage spaces shall be provided in all commercial, office, industrial, and multifamily
residential projects of more than 10 units. Minimum spaces equal to five percent of the required
automobile parking spaces or three bicycle storage spaces,whichever is greater. After the first
50 bicycle storage spaces are provided,additional storage spaces required are 2.5 percent of the
required automobile parking spaces. Warehouse distribution uses shall provide bicycle storage
spaces at a rate of 2.5 percent of the required automobile parking spaces with a minimum of a
3-bike rack. In no case shall the total number of bicycle parking spaces required exceed 100.
Where this results in a fraction of 0.5 or greater, the number shall be rounded off to the higher
whole number.
G. Landscaping
1. A detailed landscape and irrigation plan, including slope planting and model home landscaping in
the case of residential development, shall be prepared by a licensed landscape architect and
submitted for Planning Director review and approval prior to the issuance of building permits or
prior final map approval in the case of a custom lot subdivision.
2. Existing trees required to be preserved in place shall be protected with a construction barrier in _/_/_
accordance with the Municipal Code Section 19.08.110,and so noted on the grading plans. The
location of those trees to be preserved in place and new locations for transplanted trees shall be
shown on the detailed landscape plans. The applicant shall follow all of the arborist's
recommendations regarding preservation, transplanting, and trimming methods.
3. All private slopes of 5 feet or more in vertical height and of 5:1 or greater slope, but less than 2:1 _/_/_
slope, shall be, at minimum, irrigated and landscaped with appropriate ground cover for erosion
control. Slope planting required by this section shall include a permanent irrigation system to be
installed by the developer prior to occupancy.
4. All private slopes in excess of 5 feet, but less than 8 feet in vertical height and of 2:1 or greater
slope shall be landscaped and irrigated for erosion control and to soften their appearance as
follows: one 15-gallon or larger size tree per each 150 sq.ft.of slope area, 1-gallon or larger size
shrub per each 100 sq.ft.of slope area,and appropriate ground cover. In addition,slope banks
in excess of 8 feet in vertical height and 2:1 or greater slope shall also include one 5-gallon or
larger size tree per each 250 sq. ft. of slope area. Trees and shrubs shall be planted in
staggered clusters to soften and vary slope plane. Slope planting required by this section shall
include a permanent irrigation system to be installed by the developer prior to occupancy.
5. For multi-family residential and non-residential development,property owners are responsible for
the continual maintenance of all landscaped areas on-site, as well as contiguous planted areas
within the public right-of-way. All landscaped areas shall be kept free from weeds and debris and
maintained in healthy and thriving condition,and shall receive regular pruning,fertilizing,mowing,
4
Project No.DRC2006-00730
Completion Date
and trimming. Any damaged,dead,diseased,or decaying plant material shall be replaced within
30 days from the date of damage.
6. The final design of the perimeter parkways,walls,landscaping,and sidewalks shall be included in
the required landscape plans and shall be subject to Planning Director review and approval and
coordinated for consistency with any parkway landscaping plan which may be required by the
Engineering Department.
7. Landscaping and irrigation systems required to be installed within the public right-of-way on the
perimeter of this project area shall be continuously maintained by the developer.
8. All walls shall be provided with decorative treatment. If located in public maintenance areas,the
design shall be coordinated with the Engineering Department.
H. Signs
1. Directory monument sign(s)shall be provided for apartment,condominium,or town homes prior
to occupancy and shall require separate application and approval by the Planning Department
prior to issuance of building permits.
1. Environmental
1. A final acoustical report shall be submitted for Planning Director review and approval prior to the
issuance of building permits. The final report shall discuss the level of interior noise attenuation
to below 45 CNEL, the building materials and construction techniques provided, and if
appropriate, verify the adequacy of the mitigation measures. The building plans will be checked
for conformance with the mitigation measures contained in the final report.
2. The applicant shall submit certification from an acoustical engineer that all recommendations of
the acoustical report were implemented in construction, including measurements of interior and
exterior noise levels to document compliance with City standards. Certification shall be
submitted to the Building & Safety Department prior to final occupancy release of the affected
homes.
J. Other Agencies
1. The applicant shall contact the U.S. Postal Service to determine the appropriate type and location
of mailboxes. Multi-family residential developments shall provide a solid overhead structure for
mailboxes with adequate lighting. The final location of the mailboxes and the design of the
overhead structure shall be subject to Planning Director review and approval prior to the issuance
of building permits.
APPLICANT SHALL CONTACTTHE BUILDING AND SAFETY DEPARTMENT, (909)477-2710,
FOR COMPLIANCE WITH THE FOLLOWING CONDITIONS:
NOTE: ANY REVISIONS MAY VOID THESE REQUIREMENTS AND NECESSITATE ADDITIONAL REVIEW(S)
K. General Requirements
1. Submit five complete sets of plans including the following:
a. Site/Plot Plan;
b. Foundation Plan and reverse foundation plan (when applicable);
C. Floor Plan;
5
Project No.DRC2006-00730
Completion Date
d. Roof and Floor Framing Plan and reverse Roof and Floor Framing Plan(when applicable);
e. Electrical Plans(2 sets, detached) including the size of the main switch, number and size
of service entrance conductors, panel schedules, and single line diagrams;
f. Plumbing and Sewer Plans, including isometrics, underground diagrams,water and waste
diagram, sewer or septic system location, fixture units, gas piping, and heating and air
conditioning; and
g. Planning Department Project Number(DRC2006-00730)clearly identified on the outside of
all plans.
2. Submit two sets of structural calculations, energy conservation calculations, and a soils report.
Architect's/Engineer's stamp and "wet" signature are required prior to plan check submittal.
3. Contractors must show proof of State and City licenses and Workers'Compensation coverage to
the City prior to permit issuance.
4. Separate permits are required for fencing and/or walls.
L. Site Development
1. Plans shall be submitted for plan check and approved prior to construction. All plans shall be
marked with the project file number(DRC2006-00730). The applicant shall comply with the latest
adopted California Codes,and all other applicable codes,ordinances,and regulations in effect at
the time of permit application. Contact the Building and Safety Department for availability of the
Code Adoption Ordinance and applicable handouts.
2. Prior to issuance of building permits for a new residential project or major addition,the applicant
shall pay development fees at the established rate. Such fees may include,but are not limited to:
City Beautification Fee, Park Fee, Drainage Fee,Transportation Development Fee, Permit and
Plan Check Fees, Construction and Demolition Diversion Program deposit and fees and School
Fees. Applicant shall provide a copy of the school fees receipt to the Building and Safety
Department prior to permit issuance.
3. Street addresses shall be provided by the Building and Safety Official after tract/parcel map
recordation and prior to issuance of building permits.
4. Construction activity shall not occur between the hours of 8:00 p.m. and 6:30 a.m. Monday
through Saturday, with no construction on Sunday or holidays.
5. Construct trash enclosure(s) per City Standard (available at the Planning Department's public
counter).
6. Submit pool plans to the County of San Bernardino's Environmental Health Services Department
for approval.
M. New Structures
1. Provide compliance with the California Building Code (CBC) for property line clearances
considering use, area, and fire-resistiveness.
2. Provide compliance with the California Building Code for required occupancy separations.
3. Roofing material shall be installed per the manufacturer's "high wind" instructions.
4. Provide draft stops in attic areas, not to exceed 3,000 square feet, in accordance with CBC
Section 1505.
6
Project No.DRC2006-00730
Completion Date
5. Provide draft stops in attics in line with common walls.
6. Exterior walls shall be constructed of the required fire rating in accordance with CBC Table 5-A
7. Openings in exterior walls shall be protected in accordance with CBC Table 5-A.
8. If the area of habitable space above the first floor exceeds 3,000 square feet, then the
construction type shall be V-1 Hour minimum.
9. Walls and floors separating dwelling units in the same building shall be not less than 1-hour
fire-resistive construction.
N. Grading
1. Grading of the subject property shall be in accordance with California Building Code,City Grading
Standards, and accepted grading practices. The final grading plan shall be in substantial
conformance with the approved grading plan.
2. A soils report shall be prepared by a qualified engineer licensed by the State of California to
perform such work.
3. A geological report shall be prepared by a qualified engineer or geologist and submitted at the
time of application for grading plan check.
4. The final grading plan, appropriate certifications and compaction reports shall be completed,
submitted, and approved by the Building and Safety Official prior to the issuance of building
permits.
5. A separate grading plan check submittal is required for all new construction projects and for
existing buildings where improvements being proposed will generate 50 cubic yards or more of
combined cut and fill. The grading plan shall be prepared, stamped, and signed by a California
registered Civil Engineer.
O. Additional Requirements/Comments
1. Project shall fully comply with accessibility requirements of 2001 California Building Code Chapter
11A 9 Housing Accessibility).
APPLICANT SHALL CONTACT THE ENGINEERING DEPARTMENT, (909) 477-2740, FOR
COMPLIANCE WITH THE FOLLOWING CONDITIONS:
P. Dedication and Vehicular Access
1. Dedication shall be made of the following rights-of-way on the perimeter streets(measured from
street centerline):
As needed total feet on Base Line Road
2. Corner property line cutoffs shall be dedicated per City Standards.
3. Reciprocal parking agreements for all parcels and maintenance agreements ensuring joint
maintenance of all common roads, drives, or parking areas shall be provided by CC & R's or
deeds and shall be recorded prior to, or concurrent with, the final parcel map.
4. Private drainage easements for cross-lot drainage shall be provided and shall be delineated or
noted on the final map.
5. All existing easements lying within future rights-of-way shall be quit-claimed or delineated on the
final map.
7
Project No.DRC2006-00730
Completion Date
6. Easements for public sidewalks and/or street trees placed outside the public right-of-way shall be
dedicated to the City.
Q. Street Improvements
1. Pursuant to City Council Resolution No.88-557,no person shall make connections from a source
of energy,fuel or power to any building service equipment which is regulated by technical codes
and for which a permit is required unless, in addition to any and all other codes, regulations and
ordinances,all improvements required by these conditions of development approval have been
completed and accepted by the City Council,except:that in developments containing more than
one building or unit, the development may have energy connections made to a percentage of
those buildings, or units proportionate to the completion of improvements as required by
conditions of approval of development. In no case shall more than 95 percent of the buildings or
units be connected to energy prior to completion and acceptance of all improvements required by
these conditions of approval of development.
2. Construct the following perimeter street improvements including, but not limited to:
Curb& A.C. Side- Drive Street Street Comm Median Bike
Street Name Gutter Pvmt walk Appr. Lights Trees Trail Island Trail Other
Base Line Road (c) X X X
San Carmela Court X X
Atwood Street X X X X
Notes: (a) Median island includes landscaping and irrigation on meter. (b) Pavement
reconstruction and overlays will be determined during plan check. (c) If so marked, sidewalk
shall be curvilinear per Standard 114. (d) If so marked, an in-lieu of construction fee shall be
provided for this item.
3. Improvement Plans and Construction:
a. Street improvement plans, including street trees,street lights,and intersection safety lights
on future signal poles, and traffic signal plans shall be prepared by a registered Civil
Engineer and shall be submitted to and approved by the City Engineer. Security shall be
posted and an agreement executed to the satisfaction of the City Engineer and the City
Attorney guaranteeing completion of the public and/or private street improvements,prior to
final map approval or the issuance of building permits, whichever occurs first.
b. Prior to any work being performed in public right-of-way, fees shall be paid and a
construction permit shall be obtained from the City Engineer's Office in addition to any
other permits required.
C. Pavement striping, marking,traffic signing,street name signing,traffic signal conduit,and
interconnect conduit shall be installed to the satisfaction of the City Engineer.
d. Signal conduit with pull boxes shall be installed with any new construction or reconstruction _/_/_
project along major or secondary streets and at intersections for future traffic signals and
interconnect wiring. Pull boxes shall be placed on both sides of the street at 3 feet outside
of BCR, ECR, or any other locations approved by the City Engineer.
8
Project No.DRC2006-00730
Completion Date
Notes:
1) Pull boxes shall be No.6 at intersections and No.5 along streets,a maximum of 200
feet apart, unless otherwise specified by the City Engineer.
2) Conduit shall be 3-inch galvanized steel with pull rope or as specified.
e. Handicapped access ramps shall be installed on all corners of intersections per City
Standards or as directed by the City Engineer.
f. Existing City roads requiring construction shall remain open to traffic at all times with
adequate detours during construction. Street or lane closure permits are required. A cash
deposit shall be provided to cover the cost of grading and paving,which shall be refunded
upon completion of the construction to the satisfaction of the City Engineer.
g. Concentrated drainage flows shall not cross sidewalks. Under sidewalk drains shall be
installed to City Standards, except for single family residential lots.
h. Street names shall be approved by the Planning Director prior to submittal for first plan
check.
4. Street trees, a minimum of 15-gallon size or larger, shall be installed per City Standards in
accordance with the City's street tree program.
9
Project No.DRC2006-00730
Completion Date
5. Install street trees per City street tree design guidelines and standards as follows. The completed
legend (box below) and construction notes shall appear on the title page of the street
improvement plans. Street improvement plans shall include a line item within the construction
legend stating: "Street trees shall be installed per the notes and legend on sheet_(typically
sheet 1)." Where public landscape plans are required, tree installation in those areas shall be
per the public landscape improvement plans.
The City Engineer reserves the right to adjust tree species based upon field conditions and other
variables. For additional information, contact the Project Engineer.
Min.
Grow
Street Name Botanical Name Common Name Space Spacing Size City.
Base Line Road Magnolia grandiflora NCN 8' 30'0.C. 15 gal Fill
East of Have n "Samuel Sommer" Triangulated in
Avenue Foreground
Tree P.A.8'or
Greater
P.A. Less Than 8'or Magnolia grandiflora"St. NCN 3' 20'0.C. 15 gal Fill
under power Lines Mary" Triangulated in
Background Tree P.A. Pinus canariensis Canary Island Pine 8' 25'0.C. 15 gal Fill
8'or Greater Min. in
informal,
use
occasionally
behind
Magnolias
Accent Tree Ginkgo biloba Maidenhair Tree 5' 25'O.C. 15 gal Fill
"Fairmount" in
Victoria Park Lane Geijere parviflora Australian Willow 5' 20'0.C. 15 gal Fill
Parkway in
Parkway Pinus canariensis Canary Island Pine 8' 260.C. 15 gal Fill
in
Atwood Street Magnolia grandiflora"St. NCN 3' 25'O.C. 15 gal Fill
Mary" in
San Carmela Court "Pinus canariensis" Canary Island Pine 8' 25'0,C. 15 gal Fill
in
Construction Notes for Street Trees:
1) All street trees are to be planted in accordance with City standard plans.
2) Prior to the commencement of any planting,an agronomic soils report shall be furnished to
the City inspector. Any unusual toxicities or nutrient deficiencies may require backfill soil
amendments, as determined by the City inspector.
3) All street trees are subject to inspection and acceptance by the Engineering Department.
4) Street trees are to be planted per public improvement plans only.
6. Intersection line of sight designs shall be reviewed by the City Engineer for conformance with
adopted policy. On collector or larger streets, lines of sight shall be plotted for all project
intersections, including driveways. Local residential street intersections and commercial or
industrial driveways may have lines of sight plotted as required.
R. Public Maintenance Areas
1. A separate set of landscape and irrigation plans per Engineering Public Works Standards shall be
submitted to the City Engineer for review and approval prior to final map approval or issuance of
building permits, whichever occurs first. The following landscaped parkways, medians, paseos,
easements, trails or other areas shall be annexed into the Landscape Maintenance District.
2. A signed consent and waiver form to join and/or form the appropriate Landscape and Lighting
Districts shall be filed with the City Engineer prior to final map approval or issuance of building
permits whichever occurs first. Formation costs shall be borne by the developer.
10
Project No.DRC2006-00730
Completion Date
3. Parkway landscaping on the following street(s) shall conform to the results of the respective
Beautification Master Plan Base Line Road.
S. Drainage and Flood Control
1. A final drainage study shall be submitted to and approved by the City Engineer prior to final map
approval or the issuance of building permits,whichever occurs first. All drainage facilities shall
be installed as required by the City Engineer.
2. Adequate provisions shall be made for acceptance and disposal of surface drainage entering the
property from adjacent areas.
T. Utilities
1. Provide separate utility services to each parcel including sanitary sewerage system,water,gas,
electric power, telephone, and cable TV (all underground) in accordance with the Utility
Standards. Easements shall be provided as required.
2. The developer shall be responsible for the relocation of existing utilities as necessary.
3. Water and sewer plans shall be designed and constructed to meet the requirements of the
Cucamonga Valley Water District(CVW D), Rancho Cucamonga Fire Protection District,and the
Environmental Health Department of the County of San Bernardino. A letter of compliance from
the CVW D is required prior to final map approval or issuance of permits, whichever occurs first.
Such letter must have been issued by the water district within 90 days prior to final map approval
in the case of subdivision or prior to the issuance of permits in the case of all other residential
projects.
4. Approvals have not been secured from all utilities and other interested agencies involved.
Approval of the final parcel map will be subject to any requirements that may be received from
them.
U. General Requirements and Approvals
1. A non-refundable deposit shall be paid to the City,covering the estimated operating costs for all
new streetlights for the first six months of operation, prior to final map approval or prior to building
permit issuance if no map is involved.
2. Prior to the issuance of building permits,a Diversion Deposit and related administrative fees shall
be paid for the Construction and Demolition Diversion Program. The deposit is fully refundable if
at least 50% of all wastes generated during construction and demolition are diverted from
landfills,and appropriate documentation is provided to the City. Form CD-1 shall be submitted to
the Engineering Department when the first building permit application is submitted to Building and
Safety. Form CD-2 shall be submitted to the Engineering Department within 60 days following
the completion of the construction and/or demolition project.
APPLICANT SHALL CONTACT THE FIRE SAFETY DEPARTMENT, FIRE PROTECTION
PLANNING SERVICES AT, (909) 477-2770, FOR COMPLIANCE WITH THE FOLLOWING
CONDITIONS:
SEE ATTACHED
tt
Rancho Cucamonga Fire Protection District
Fire Construction Services
STANDARD CONDITIONS
September 21, 2006
Vineyards at Victoria Park Place
Base Line Rd &Victoria Park
MFR & SFR Development
SUBT718212 & DRC2006-00730
THE FOLLOWING STANDARD CONDITIONS APPLY TO THIS PROJECT.
The RCFPD Procedures & Standards which are referenced in this document can be access on
the web at http://www.ci.rancho-cucamonga.ca.us/fire/index.htm under the Fire Safety Division
& Fire Construction Services section. Search by article; the preceding number of the standard
refers to the article. Chose the appropriate article number then a drop down menu will appear,
select the corresponding standard.
FSC-1 Public and Private Water Supply
1. Design guidelines for The Fire Protection water supply must be in accordance to RCFPD
Standard 9-8: The following provides design guidelines for the spacing and location of fire
hydrants:
a. The maximum distance between fire hydrants in multi-family residential projects is
400-feet. No portion of the exterior wall shall be located more than 200-feet from an
approved fire hydrant. For cul-de-sacs, the distance shall not exceed 150-feet.
b. Fire hydrants are to be located. The preferred locations for fire hydrants are:
i. At the entrance(s) to a residential project from the public roadways.
ii. At intersections.
iii. On the right side of the street, whenever practical and possible.
iv. As required by the Fire Safety Division to meet operational needs of the Fire
District.
V. A minimum of forty-feet (40')from any building.
C. If any portion of a facility or building is located more than 150-feet from a public fire
hydrant measured on an approved route around the exterior of the facility or building,
additional private or public fire hydrants and mains capable of supplying the required
fire flow shall be provided.
d. Provide one fire hydrant for each 1000 gpm of required fire flow or fraction thereof.
FSC-2 Fire Flow
1. The required minimum fire flow for this project, when automatic fire sprinklers are installed
is 1500 gallons per minute at a minimum residual pressure of 20-pounds per square inch.
This flow reflects a 50-percent reduction for the installation of an approved automatic fire
sprinkler system in accordance with NFPA 13 or 13R with central station monitoring. This
requirement is made in accordance with the California Fire Code Appendix III-A, as
adopted by the Fire District Ordinances.
2. The required minimum fire flow for structures located in the designated hazardous fire
area shall be not less than 1,750 gpm at 20-psi residual. For structures in excess of
36,000 square feet use CFC Table A-III-A-1.
3. Public fire hydrants located within a 500-foot radius of the proposed project may be used
to provide the required fire flow subject to Fire District review and approval. Private fire
hydrants on adjacent property shall not be used to provide required fire flow. .
4. Fire Protection water plans are required for all projects that must extend the existing water
supply to or onto the site. Building permits will not be issued until fire protection
water plans are approved.
5. On all site plans to be submitted for review, show all fire hydrants located within 600-feet
of the proposed project site.
FSC-3 Prerequisite for submittal of Overhead Automatic Fire Sprinkler Systems
1. Prior to submitting plans for an overhead automatic fire sprinkler system, the applicant
shall submit plans, specifications and calculations for the fire sprinkler system
underground supply piping. Approval of the underground supply piping system in
accordance to RCFPD Standard #9-8 must be obtained prior to submitting the overhead
fire sprinkler system plans.
FSC-4 Requirements for Automatic Fire Sprinkler Systems
Rancho Cucamonga Fire District Ordinance 15, the 2001 California Fire Code and/or any other
applicable standards require an approved automatic fire sprinkler system to be installed in:
1. Multifamily structures greater than 7,500 square feet.
2. Multi-family residential structures in excess of 4 units.
3. When required fire flow cannot be provided due to inadequate volume or pressure.
4. When any applicable code or standard requires the structure to be sprinklered.
FSC-5 Fire Alarm System
1. RCFPD Ordinance 15, based on use or floor area (or by other adopted codes or
standards) may require an automatic and/or manual fire alarm system. Refer to RCFPD
Ordinances 15 and 39, the California Building Code, RCFPD Fire Alarm Standard #10-6
and/or the California Fire Code.
2. Prior to the installation of the fire alarm system, Fire Construction Services' approval and a
building permit must be obtained. Plans and specifications shall be submitted to Fire
Construction Services in accordance with RCFPD Fire Alarm Standard #10-6.
2
FSC-6 Fire District Site Access
Fire District access roadways include public roads, streets and highways, as well as private
roads, streets drive aisles and/or designated fire lanes. Please reference the RCFPD Fire
Department Access — Fire Lanes Standard #9-7.
1. Location of Access: All portions of the structures 1s` story exterior wall shall be located
within 150-feet of Fire District vehicle access, measure on an approved route around the
exterior of the building. Landscaped areas, unpaved changes in elevation, gates and
fences are deemed obstructions.
2. Specifications for private Fire District access roadways per the RCFPD Standards
are:
a. The minimum unobstructed width is 26-feet.
b. The maximum inside turn radius shall be 20-feet.
C. The minimum outside turn radius shall be 46-feet.
d. The minimum radius for cul-de-sacs is 45-feet.
e. The minimum vertical clearance is 14-feet, 6-inches.
f. At any private entry median, the minimum width of traffic lanes shall be 20-feet on
each side.
g. The angle of departure and approach shall not exceed 9-degrees or 20 percent.
h. The maximum grade of the driving surface shall not exceed 12%.
i. Support a minimum load of 70,000 pounds gross vehicle weight (GVW).
j. Trees and shrubs planted adjacent to the fire lane shall be kept trimmed to a
minimum of 14-feet, 6-inches from the ground up. Vegetation shall not be allowed to
obstruct Fire Department apparatus.
3. Access Doorways: Approved doorways, accessible without the use of a ladder, shall be
provided in accordance with the 2001 California Building Code, Fire and/or any other
applicable standards.
4. Access Walkways: Hardscaped access walkways shall be provided from the fire
apparatus access road to all required building exterior openings.
5. Residential gates installed across Fire District access roads shall be installed in
accordance with RCFPD Residential Gate Standard #9-1. The following design
requirements apply:
a. Prior to the fabrication and installation of the gates, plans are required to be
submitted to Fire Construction Services (FCS) for approval. Upon the completion of
the installation and before placing the gates in service, inspection and final
acceptance must be requested from FCS.
b. Gates must slide open horizontally or swing inward.
3
C. Gates may be motorized or manual.
d. When fully open, the minimum clearance dimension of drive access shall be 20 feet.
e. Manual gates must be equipped with a RCFPD lock available at the Fire Safety
Office for $20.00.
f. Motorized gates must open at the rate of one-foot per second.
g. The motorized gate actuation mechanism must be equipped with a manual override
device and a fail-safe or battery backup feature to open the gate or release the
locking Mechanism in case of power failure or mechanical malfunction.
h. Motorized gates shall be equipped with a Knox override key switch. The switch must
be installed outside the gate in a visible and unobstructed location.
i. For motorized gates, a traffic loop device must be installed to allow exiting from the
complex. If traffic pre-emption devices (TPD) are to be installed, the device, location
and operation must be approved by the Fire Chief prior to installation. Bi-directional
or multiple sensors may be required due to complexity of the various entry
configurations.
6. Fire Lane Identification: Red curbing and/or signage shall identify the fire lanes. A site
plan illustrating the proposed delineation that meets the minimum Fire District standards
shall be included in the architectural plans submitted to B&S for approval.
7. Approved Fire Department Access: Any approved mitigation measures must be clearly
noted on the site plan. A copy of the approved Alternative Method application, if
applicable, must be reproduced on the architectural plans submitted to B&S for plan
review.
8. Roof Access: There shall be a means of fire department access from the exterior walls
of the buildings on to the roofs of all commercial, industrial and multi-family residential
structures with roofs less than 75' above the level of the fire access road.
a. This access must be reachable by either fire department ground ladders or by an
aerial ladder.
b. A minimum of one ladder point with a fixed ladder shall be provided in buildings with
construction features, or high parapets that inhibit roof access.
C. The number of ladder points may be required to be increased, depending on the
building size and configuration.
d. Regardless of the parapet height or construction features the approved ladder point
shall be identified in accordance to the roof access standard.
e. Where the entire roof access is restricted by high parapet walls or other obstructions,
a permanently mounted access ladder is required.
f. Multiple access ladders may be required for larger buildings.
g. Ladder construction must be in accordance with the RCFPD Roof Access Standard
9-9 Appendix A and drawings 9-9a and 9-9b.
4
h. A site plan showing the locations of the roof ladder shall be submitted during plan
check.
i. Ladder points shall face a fire access roadway(s).
FSC-10 Occupancy and Hazard Control Permits
Listed are those Fire Code permits commonly associated with the business operations and/or
building construction. Plan check submittal is required with the permit application for approval
of the permit; field inspection is required prior to permit issuance. General Use Permit shall be
required for any activity or operation not specifically described below, which in the judgment of
the Fire Chief is likely to produce conditions that may be hazardous to life or property.
• Tents, Canopies and/or Air Supported Structures
• Liquefied Petroleum Gases
FSC-13 Alternate Method Application
Fire Construction Services staff and the Fire Marshal will review all requests for alternate
method, when submitted. The request must be submitted on the Fire District "Application for
Alternate Method" form along with supporting documents and payment of the $92 review fee.
FCS-14 Map Recordation
1. RECIPROCAL AGREEMENTS for Fire Department Emergency Access and Water Supply
are required on this project. The project appears to be located on a property that is being
subdivided. The reciprocal agreement is required to be recorded between property
owners and the Fire District. The recorded agreement shall include a copy of the site
plan. The Fire Construction Services shall approve the agreement, prior to recordation.
The agreement shall be recorded with the County of San Bernardino, Recorders Office.
Reciprocal access agreement — Please provide a permanent access agreement
between the owners granting irrevocable and a non-exclusive easement, favoring the Fire
District to gain access to the subject property. The agreement shall include a statement
that no obstruction, gate, fence, building or other structure shall be placed within the
dedicated access, without Fire Department approval. The agreement shall have provisions
for emergency situations and the assessing of cost recovery to the property by the fire
District.
Reciprocal water covenant — Please provide a permanent maintenance and service
covenant between the owners granting an irrevocable and non-exclusive easement,
favoring the Fire District for the purpose of accessing and maintaining the private water
mains, valves and fire hydrants (fire protection systems facilities in general). The covenant
shall have provisions for emergency situations and the assessing of cost recovery to the
property by the fire District.
Chronological Summary of RCFPD Standard
Conditions
PRIOR TO ISSUANCE OF BUILDING PERMITS — Please complete the following prior to
the issuance of any building permits:
1. Private Water Supply (Fire) Systems: The applicant shall submit construction plans,
specifications, flow test data and calculations for the private water main system for review
5
and approval by the Fire District. Plans and installation shall comply with Fire District
Standards. Approval of the on-site (private) fire underground and water plans is required
prior to any building permit issuance for any structure on the site. Private on-site
combination domestic and fire supply system must be designed in accordance with
RCFPD Standards # 9-4, #10-2 and #10-4. The Building & Safety Division and Fire
Construction Services will perform plan checks and inspections.
All private on-site fire hydrants shall be installed, flushed and operable prior to delivering
any combustible framing materials to the site. Fire construction Services will inspect the
installation, witness hydrant flushing and grant a clearance before lumber is dropped.
2. Public Water Supply (Domestic/Fire) Systems: The applicant shall submit a plan
showing the locations of all new public fire hydrants forthe review and approval by the
Fire District and CCWD. On the plan, show all existing fire hydrants within a 600-foot
radius of the project. All required public fire hydrants shall be installed, flushed and
operable prior to delivering any combustible framing materials to the site. CCWD
personnel shall inspect the installation and witness the hydrant flushing. Fire Construction
Services shall inspect the site after acceptance of the public water system by CCWD. Fire
Construction Services must grant a clearance before lumber is dropped.
3. Construction Access: The access roads must be paved in accordance with all the
requirements of the RCFPD Fire Lane Standard #9-7. All temporary utilities over access
roads must be installed at least 14' 6" above the finished surface of the road.
4. Fire Flow: A current fire flow letter from CCWD must be received. The applicant is
responsible for obtaining the fire flow information from CCWD and submitting the letter to
Fire Construction Services.
5. Easements and Reciprocal Agreements: All easements and agreements must be
recorded with the County of San Bernardino.
PRIOR TO THE RELEASE OF TEMPORARY POWER
The building construction must be substantially completed in accordance with Fire Construction
Services' "Temporary Power Release Checklist and Procedures".
PRIOR TO OCCUPANCY OR FINAL INSPECTION — Please complete the following:
1. Hydrant Markers: All fire hydrants shall have a blue reflective pavement marker
indicating the fire hydrant location on the street or driveway in accordance with the City of
Rancho Cucamonga Engineering Standard Plan 134, "Installation of Reflective Hydrant
Markers". On private property, the markers shall be installed at the centerline of the fire
access road, at each hydrant location.
2. Private Fire Hydrants: For the purpose of final acceptance, a licensed sprinkler
contractor, in the presence of Fire Construction Services, shall conduct a test of the most
hydraulically remote on-site fire hydrants. The underground fire line contractor, developer
and/or owner are responsible for hiring the company to perform the test. A final test
report shall be submitted to Fire Construction Services verifying the fire flow available.
The fire flow available must meet or exceed the required fire flow in accordance with the
California Fire Code.
3. Fire Sprinkler System: Prior to the issuance of a Certificate of Occupancy, the fire
sprinkler system(s) shall be tested and accepted by Fire Construction Services.
6
4. Fire Sprinkler Monitoring: Prior to the issuance of a Certificate of Occupancy, the fire
sprinkler monitoring system must be tested and accepted by Fire Construction Services.
The fire sprinkler monitoring system shall be installed, tested and operational immediately
following the completion of the fire sprinkler system (subject to the release of power).
5. Fire Alarm System: Prior to the issuance of a Certificate of Occupancy, the fire alarm
system shall be installed, inspected, tested and accepted by Fire Construction Services.
6. Access Control Gates: Prior to the issuance of a Certificate of Occupancy, vehicular
gates must be inspected, tested and accepted in accordance with RCFPD Standards #9-
1 or#9-2 by Fire Construction Services.
7. Fire Access Roadways: Prior to the issuance of any Certificate of Occupancy, the fire
access roadways must be installed in accordance with the approved plans and acceptable
to Fire Construction Services.
The CC&R's, the reciprocal agreement and/or other approved documents shall be
recorded and contain an approved fire access roadway map with provisions that prohibit
parking, specify the method of enforcement and identifies who is responsible for the
required annual inspections and the maintenance of all required fire access roadways.
8. Address: Prior to the granting of occupancy, single-family dwellings shall post the
address with minimum 4-inch numbers on a contrasting background. The numbers shall
be internally or externally illuminated during periods of darkness. The numbers shall be
visible from the street. When building setback from the public roadway exceeds 100-feet,
additional 4-inch numbers shall be displayed at the property entry.
9. Address: Prior to the issuance of a Certificate of Occupancy, commercial/industrial and
multi-family buildings shall post the address with minimum 8-inch numbers on contrasting
background, visible from the street and electrically illuminated during periods of darkness.
When the building setback exceeds 200 feet from the public street, an additional non-
illuminated 6-inch minimum number address shall be provided at the property entrance.
Larger address numbers will be required on buildings located on wide streets or built with
large setbacks in multi-tenant commercial and industrial buildings. The suite designation
numbers and/or letters shall be provided on the front and back of all suites.
10. Confidential Business Occupancy Information: The applicant shall complete the
Rancho Cucamonga Fire District "Confidential Business Occupancy Information" form.
This form provides contact information for Fire District use in the event of an emergency
at the subject building or property. This form must be presented to the Fire Construction
Services Inspector.
11. Mapping Site Plan: Prior to the issuance of a Certificate of Occupancy, a 8 %' x 11" or
11" x 17" site plan of the site in accordance with RCFPD Standard #13-1 shall be revised
by the applicant to reflect the actual location of all devices and building features as
required in the standard. The site plan must be reviewed and accepted by the Fire
Inspector.