1, CONDUIT.
A. MINIMUM COVER IN STREET OR PARKWAY IS 30" BELOW GUTTER GRADE, UNLESS NOTED OTHERWISE.
B. MINIMUM COVER ON PRIVATE PROPERTY IS 30" BELOW FINISHED GRADE, UNLESS NOTED OTHERWISE.
C. CAP ALL MAINLINE CONDUITS AND SERVICE CONDUITS.
D. INSTALL BLANK CONDUIT PLUGS IN ALL CONDUITS TERMINATING INTO VAULTS, MANHOLES, PMH'S,
SOE'S & ALL CAP LOCATIONS, PER CITY SPECIFICATIONS.
E. INSTALL PULL ROPE IN ALL CONDUIT RUNS. PULL ROPE TO BE 3/16" POLYPROPYLENE OR
POLYETHYLENE ROPE, BRAIDED OR TWISTED.
F. ALL CONDUIT MUST BE MANDRELLED.
2. CONDUIT RADIUS REQUIREMENTS:
A. THE MINIMUM RADIUS FOR BENDS ARE::
36" FOR CONDUITS 3" IN DIAMETER OR SMALLER
48" FOR CONDUITS 4" AND 5" IN DIAMETER
60" FOR CONDUITS 6" IN DIAMETER
B. THE MINIMUM RADIUS FOR ALL SWEEPS OF ALL MAINLINE CONDUITS IS 12'-6" (UNLESS NOTED
OTHERWISE).
3. EXCAVATION AND BACKFILL:
A. WORK AREA SHALL BE CLEARED AND ROUGH GRADED TO WITHIN 4" OF FINAL GRADE PRIOR TO
INSTALLATION OF CITY CONDUIT OR STRUCTURES.
B. ALL EXCAVATIONS SHALL BE IN ACCORDANCE WITH THE CALIFORNIA STATE CONSTRUCTION SAFETY
ORDERS (WHEN APPLICABLE), CITY SPECIFICATIONS, AND ALL GOVERNING LOCAL ORDINANCES.
C. EACH TRENCH TO BE A UNIFORM DEPTH BELOW FINAL GRADE PRIOR TO INSTALLATION OF CITY
CONDUIT OR STRUCTURES,
D. BACKFILL SHALL BE PROVIDED BY THE CONTRACTOR FOR ALL EXCAVATIONS AND SHALL INCLUDE
CRUSHED ROCK, CONCRETE, AND/OR IMPORTED BACKFILL, WHEN REQUIRED.
E. BACKFILL WITH A MINIMUM OF ONE SACK PER YARD SAND CEMENT SLURRY AROUND AND OVER
VAULTS AND MANHOLES AND AROUND PMH'S WITHIN ONE FOOT OF FINISHED GRADE.
F. BACKFILL SHALL IMMEDIATELY FOLLOW SUBSTRUCTURE INSTALLATION. AT NO TIME SHALL CABLE BE
LEFT EXPOSED OVER 24 HOURS.
G. NO ROCKS ARE ALLOWED WITHIN 12" OF DIRECT -BURIED CABLES OR ANY CONDUIT WITHOUT CONCRETE
ENCASEMENT.. NATIVE BACKFILL DOES NOT PASS THROUGH A 1/2" SCREEN, PLACE IMPORTED SAND
3" BELOW AND 12" ABOVE CITY CABLES. AFTER THIS POINT, NO ROCKS LARGER THAN 12" IN
DIAMETER ARE PERMITTED.
H. ALL BACKFILL SHALL BE COMPACTED TO MEET OR EXCEED LOCAL ORDINANCES OR OTHER
REQUIREMENTS. IT SHALL BE PLACED IN A MANNER THAT WILL NOT DAMAGE THE CONDUIT OR
SUBSTRUCTURE OR ALLOW FUTURE SUBSIDENCE OF THE TRENCH OR STRUCTURES.,
4. PAVING:
REPAVING, WHERE REQUIRED, SHALL BE PLACED IN SUCH A MANNER THAT INTERFERENCE WITH TRAFFIC,
INCLUDING PEDESTRIAN TRAFFIC, WILL BE KEPT TO A MINIMUM. THE CONTRACTOR SHALL ESTABLISH A
PROGRAM OF REPAVING ACCEPTABLE TO THE MUNICIPALITY, COUNTY, OR OTHER AUTHORITY HAVING
JURISDICTION AND WHICH IS ACCEPTABLE TO THE CITY.
5. STRUCTURES:
A. ALL SUBSTRUCTURES SHALL BE CONSTRUCTED OR INSTALLED TO CITY SPECIFICATIONS,
B. INSTALL PROTECTION BARRIERS, WHEN REQUIRED, IN AREAS EXPOSED TO TRAFFIC, PER CITY
INSPECTOR
C. ALL CONDUIT LINES AND CONCRETE FLOORED SUBSTRUCTURES SHALL BE WATER TIGHT.
D. ALL GROUNDING MATERIALS SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.
E. CONTRACTOR TO PROVIDE SUBSTRUCTURE ENCLOSURE WALL DETAILS TO CITY INSPECTOR FOR
APPROVAL PRIOR TO INSTALLATION.
6.RETAINING WALLS:
WHEN REQUIRED, RETAINING WALLS SHALL BE PROVIDED BY THE CONTRACTOR. WALLS ARE REQUIRED
WHEREVER GRADE RISES MORE THAN 18" ABOVE THE STRUCTURE OR 24" ABOVE THE PAD SURFACE AT A
DISTANCE OF 5' FROM THE SAME, OR IN AREAS SUBJECT TO EROSION. DESIGN AND INSTALLATION MUST
COMPLY WITH LOCAL BUILDING ORDINANCES. REFER TO CITY INSPECTOR FOR TYPICAL SPACE
REQUIREMENTS.
7. ACCESS:
HEAVY TRUCK ACCESS SHALL BE MAINTAINED TO EQUIPMENT LOCATIONS. STRUCTURES MUST BE CLEAR OF
ALL APPURTENANCES THAT WOULD OBSTRUCT THE LOADING OR UNLOADING OF EQUIPMENT.
&SERVICES:
E. METERS AND SERVICES SHALL COMPLY WITH CITY SERVICES REQUIREMENTS.
F. WIRING MUST BE IN ACCORDANCE WITH APPLICABLE LOCAL ORDINANCES AND APPROVED BY LOCAL
INSPECTION AUTHORITIES.
9. LOCATION:
A. THE LOCATION OF EXCAVATIONS AND STRUCTURES FOR THE CITY SHALL BE SHOWN ON THE WORKING
DRAWING. NO DEVIATION FROM THE PLANNED LOCATIONS WILL BE PERMITTED UNLESS APPROVED BY
THE CITY INSPECTOR.
B. ACTUAL LOCATION OF OBSTRUCTIONS, STORM DRAINS, AND/OR OTHER FOREIGN UTILITIES TO BE THE
RESPONSIBILITY OF THE CONTRACTOR.
10. CONTRACTOR TO VERIFY LOCATION AND WIDTHS OF ALL SIDEWALKS AND DRIVEWAYS WITH THE APPROVED
STREET IMPROVEMENT PLANS, APPROVED STREET LIGHT PLANS AND THE ACTUAL FIELD CONDITIONS, PRIOR
TO STREET LIGHT INSTALLATION.
11. SURVEY:
SURVEYING OF STREET IMPROVEMENTS SHALL BE PERFORMED BY THE CITY, PROPERTY CORNERS, LOT
LINES, FINISHED GRADE, ETC., NECESSARY FOR THE INSTALLATION OF UNDERGROUND FACILITIES MUST BE
COMPLETED AND MARKERS OR STAKES PLACED PRIOR TO THE START OF THE INSTALLATION. IN ADDITION,
CONTRACTOR SHALL MAINTAIN THE MARKERS DURING THE INSTALLATION AND INSPECTIONS BY INSPECTION
BY CITY. GRADE AND PROPERTY LINE STAKES MUSH SHOW ANY OFFSET MEASUREMENTS.
12.COORDINATION AND SUPERVISION:
THE CONTRACTOR SHALL PROVIDE SUPERVISION OVER AND COORDINATION AMONG THE VARIOUS
CONTRACTORS WORKING WITHIN THE DEVELOPMENT IN ORDER TO PREVENT DAMAGE TO CITY FACILITIES,
CONTRACTOR IS RESPONSIBLE FOR THE COST OF REPAIRS, REPLACEMENT, RELOCATION, OR OTHER
CORRECTIONS TO CITY FACILITIES MADE NECESSARY BY THEER FAILURE TO PROVIDE SUPERVISION OR TO
OTHERWISE COMPLY WITH THESE SPECIFICATIONS.
13.OTHER UTILITY REQUIREMENTS:
THE DRAWING PREPARED FOR THIS JOB MAY ALSO COVER THE FACILITIES TO BE INSTALLED FOR OTHER
UTILITY. ANY QUESTIONS CONCERNING DETAILS OF THEIR INSTALLATION SHOULD BE REFERRED TO THE
COMPANY CONCERNED.
14.WARRANTY:
CONTRACTOR EXPRESSLY REPRESENT AND WARRANTY THAT ALL WORK PERFORMED AND ALL MATERIAL
USED IN MEETING CONTRACTOR'S OBLIGATIONS, HEREIN, ARE FREE FROM DEFECTS IN WORKMANSHIP AND
ARE CONFORMITY WITH CITY REQUIREMENTS. THIS WARRANTY SHALL COMMENCE UPON RECEIPT BY
CONTRACTOR OF CITY'S FINAL ACCEPTANCE AND SHALL EXPIRE ONE YEAR FROM THAT DATE. CONTRACTOR
AGREES TO PROMPTLY CORRECT TO THE CITY'S SATISFACTION AND THAT OF ANY GOVERNMENTAL AGENCY
HAVING JURISDICTION AND AT CONTRACTOR'S EXPENSE ANY BREACH OF THIS WARRANTY WHICH MAY
BECOME APPARENT THROUGH INSPECTION OR OPERATION OF UNDERGROUND ELECTRIC SYSTEM BY CITY
DURING THIS WARRANTY PERIOD.
15.INSPECTION:
INSPECTION IS REQUIRED DURING THE CONSTRUCTION PERIOD. A 48 HOUR ADVANCE NOTICE OF INTENT TO
START CONSTRUCTION IS REQUIRED FROM THE CONTRACTOR TO THE CITY OF RANCHO CUCAMONGA. PHONE:
909-477-2740 X4080
16.AS-BUILTS:
CONTRACTOR RESPONSIBLE TO MAINTAIN AS -BUILT DRAWINGS WHICH ARE TO BE UPDATED DAILY,
CONTRACTORS SHALL KEEP AND MAINTAIN TWO COPIES OF THE AS-BUILTS. ONE SET IS FOR THE
CONTACTOR AND THE SECOND SET IS FOR THE CITY INSPECTOR.
MY�POWER PRODUCTS,INC 90 -5'-1800
2950 E. PHILADEL.PHIA ST, DNTARID CA 91761-8545
r^T kIr1 MF1 JFi1 AA-'11--mPf)n (mnn)
UN -METERED PEDESTAL DETAIL
D G!
R F
DIAL TO 110111 wG
BEFORE DAYS BEFM
YOU DIG You DIG
TOLL FREE 800-227-2600
A PUBLIC SERVICE BY
UNDERGRO M SERMCE ALERT OF SOUMERN CALJFORMA
W
FRONT VIEW
i
I I
1 I
NOTE:
ENCLOSURE TO BE GROUNDED PER r �
LOCAL CODE. V t lip
I
t�I
FINISH
GRADE t
J�
MIN.
00 I{ III
OD
11 1 1-111I�II I�II�ISIII
120 VOLT WIRE IN
CONDUIT (PER LOCAL CODE) -�
TO POWER SIDE OF ENCLOSURE
i0E VIEW
FINISH
GRADE
W SCH 40 CON
's
METERED ENCLOSURE
STRONG BOX MODEL NO.
M PS -SERIES
NOTE -
METER TO FACE STREET
900' SWEEP ELL S"
(IYP.)
I a I
3' X 3' X 6" CONCRETE
FOOTING INSTALL A MINIMUM
OF 3" ABOVE GRADE AND
SLOPE TOP TO DRAIN AT
MINIMUM OF 2%,
120 VOLT WIRE IN
CONDUIT (PER LOCAL CODE)
TO IRRIGATION CONTROLLER
ENCLOSURE
NOTE:
ALL CONTROLLER CABINET SHALL BE
PRE -ASSEMBLED, TESTED AND INSPECTED
MELD BY CALSENSE,
C METER PER SCE
) ROC?
CITY OF RANCHO CUCAMONGA, CALIFORNIA
N APPROVED BY:
STANDARD PLAN
I*AE
METER ENCLOSURE 52
INEE USE WITH STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION
R.C.E. 53672 SHEET 1 OF 1
NOTE: METER
PEDESTAL FOR THIS
PROJECT IS TO BE
UN -METERED, LS-2
12-1/2" Bolt Circle Diameter
1"0 F1554 Grade 36 anchor rods
(Total 4) with Grade A hot -dip A563
hex nuts, with ASTM F436 type 1 washers,
8 UNC threads 6" long both ends
12"x12" ASTM A-36 Base Plate
L
Thickness= 1" for 23' Pole
Thickness= 1-1/4" for 28' Pole
15" �I
111"
Concrete Cap
33"x30" curb adjacent
-
o
with cold joint perimeter
2%
Bock of
curb
1" Max. bottom of nut
Ja
to top of footing
'
Depth of Footing
See Table Below��
1-1/2" Conduit
#4 @ 6" for
Spiral Reinforcement
3" Clear (Typ.) from
spiral reinforcement
to the pile edge
3" Clear °
Diameter
85 MPH WIND ZONE
a�
E
a
Q Ameron Pole
See Sheet 1
F_ Type S Mortar
24"
I I-•-- Pale
2q
39" 48"
Min. I
Top of
Curb
Flaw Line
30" Min. Below
Flow Line (Typ.)
�- 2"x2%1/4" Plate
Washer (Typ))
Tack Weld or Peen
6-#6 Equally spaced
Vertical Bars
DEPTH OF FOOTING TABLE FOR CONSTRAINED
AND NON -CONSTRAINED SURFACE CONDITIONS
Soil Type ;per UBC
23' Pole
2$' Pole
and Geotechnital Report
III.
Sandy Gravel, Gravel
IV.
{Sand, Silty Sand, Clayey Sand,
� Silty Gravel, Clayey Gravel
V.
Clay, Sandy Clay,
Special Design
Silt Clay, Clayey Silt Y Y.
per Geotechnical Report
DWG. NOT
TO SCALE
r`
�o
CITY OF RANCHO CUCAMONGA, CALIFORNIA
APPROVED BY: STREET LIGHTS AND STANDARD PLAN
n 3i',+?
FOUNDATION DETAILS 410
UjCITY ENGI E DATE USE WITH STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION SHEET 2 OF 2
R.C.E. 67514
ALUMINUM CAP'-
ARM
INN
T
T
Ca
Uj
uj
rY
LENGTH
LLo IGHTING FIXTURE CATALOG
CITY STANDARDS
(j)
0
0
0
LLI
Z
Q
J
E. 9TH ST Q
LL
co
FERON B VD.
LU E. 8TH ST z
LLi
LU
Uj Q � < Q
d d
w Z � E. 6TH ST. co
m
Z J U W
E. 4TH ST.�
VICINITY MAP
CONSTRUCTION NOTES
LEGEND:
CONSTRUCT 240V 51 WATT LED 580OLUMEN STREET LIGHT ON
POLE DESIGNATION 1C1-23 WITH LUMINAIRE: EATON
3 EA
CATALOG# VERD-AO18 D-U-T3-4N7-AP-51w-SUNTECH ELL-124,
...PER CITY OF RANCHO CUCAMONGA STD. 410. STREET LIGHTS
ARE LS-2. SEE SHEET 1 OF 2
Pa
BROOKS NO. 3 1/2 PULL BOX PER CITY STANDARDS, WITH LID
STAMPED STREET LIGHTING
4 EA.
1 1/2" PVC SCHEDULE 40 CONDUIT WITH 2#8 CU &1#8 CU
494 LF
GRND (XHHW 2).
®
INSTALL 200A 120/240v 1 PH 3W UN -METERED PEDESTAL
1 EA
PER DETAILS ON SHEET 1 OF 2. INSTALL 4" HELVETICA
ADDRESS NUMBER ON ENCLOSURE FOR STREET
LIGHTINGS
STUB CONDUIT TO P.L. FOR
POSSIBLE FUTURE USE
M
,001-00{
WIVI
EXISTING 8" G&G `
f—
EXISTING 8" C&&: z
j _ + U) -1
DIAL 7WO1 WORKING
BEFORE DAYS BEFORE
YOU DIG You De
TOLL FREE 800--ZA I' LOW
A PUBWG SERVICE BY
U1111WERGRO? SERVICE ALERT OF SOIJhi IERIN DALFORMA
Z
0
U
W
Z
J
Q
Z
O
C0
U
W
LL X
00
W
w
in
CL
W
Z Z
a U)
0
LU
1
C/)
w
Z
w [�
2
W w
W
U W
vaLr,
w
?
O I—
OOf
Nco
wz
J
Z)
0
U
o
o
d
0
/0
w
us
1621
Is=-��_ -�—'
-91
2 " PVC SCHED 40
P- W/2#8 CU &1#8 CU GRIND
j - PCB NEW 200A 120/240V
1 PHASE 3 WIRE
STREET LIGHT
PEDESTAL 'SLP'
s
1/2" PVt SCHED 48 3 65
2
STREET I IGHTINrn PI AN
�JV/"1LL. I —JV -V )
LEGEND:
CONSTRUCT 240V 51 WATT LED 580OLUMEN STREET LIGHT ON
3 EA.
POLE DESIGNATION 1C1-23 WITH LUMINAIRE: EATON
CATALOG# VERD-AO18 D-U-T3-4N7-AP-51w-SUNTECH ELL-124,
...PER CITY OF RANCHO CUCAMONGA STD, 410. STREET LIGHTS
ARE LS-2. SEE SHEET 1 OF 2
FP B
BROOKS NO. 3 1/2 PULL BOX PER CITY STANDARDS, WITH' LID
STAMPED STREET LIGHTING
4 EA.
1 1/2" PVC SCHEDULE 40 CONDUIT WITH 2#8 CU &1#8 CU GRND
(XHHW-2).
494 LF
INSTALL 200A 120/240v 1 PH 3W UN -METERED PEDESTAL
1 EA.
PER DETAILS ON SHEET 1 OF 2. INSTALL 4" HELVETICA
ADDRESS NUMBER ON ENCLOSURE FOR STREET LIGHTINGS
�— EXISTING 8" C&G
21'
44' El
8+00
23'
EXISTIN Q E (" &Q_ _
El
H
GRAPHIC SCALE
(SCALE 1 30'-0")
NEW NEMA 3R 200A 120/240V 1 P 3W PEDESTAL
'SLP'
1 1/2" PVC 40
2#8 CU
&1 #8CU GRIND
(3) NEW STREET
LIGHTS (CKT 1,3)
UTILITY
SERVICE
POINT
SINGLE LINE DIAGRAM
Service Pedestal 'SLP' LS-2 Uri -Metered
Rating: 200 amp
Main: 200/2
Served From: SCE
Voltage: 120/240 Volt
AIC: 10k aic
Feeder Size: PER SCE
Phase: 1 Phase 3 Wire
Locate: Feron Blvd West of Industrial
Ckt
No
oaf
VA
Load Description
LCL
C/B
C/B
LCL
Load Description
Load
VA
Ckt
No
1
86
3-Street Lts
100%
20/2
2
3
86
" "
100%
4
5
6
7
$
9
--
10.
11
12
Phase A: 86 VA
Total VA: 172
Total
Line Amps
Phase B: 86 VA
+LCL: 43
Total VA: 215
0.9 ames
* - Provide handle ties on all multiwire branch circuits.